Water-cooled chassis power units for common cooling circuits
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Minimum cable lengths for parallel connection and connection to a motor with a single-winding
system
Note
Minimum cable lengths
The minimum cable lengths specified in the tables below must be observed when two or
more Motor Modules are connected in parallel and there is a connection to a motor with a
single-winding system. If the cable length required for the application cannot be achieved, a
motor reactor must be provided.
Table 6- 20
6SL3325-1TE32-1AA3
6SL3325-1TE32-6AA3
6SL3325-1TE33-1AA3
6SL3325-1TE35-0AA3
6SL3325-1TE37-5AA7
6SL3325-1TE41-0AA7
6SL3325-1TE41-2AA7
6SL3325-1TE41-4AA7
Table 6- 21
6SL3325-1TG31-0AA3
6SL3325-1TG31-5AA3
6SL3325-1TG32-2AA3
6SL3325-1TG33-3AA3
6SL3325-1TG34-7AA7
6SL3325-1TG35-8AA7
6SL3325-1TG38-1AA7
6SL3325-1TG41-0AA7
6SL3325-1TG41-3AA7
6SL3325-1TG41-6AA7
Water-cooled chassis power units for common cooling circuits
Manual, 08/2017, 6SL3097-4AM10-0BP0
Motor Modules, DC 510 ... 720 V (line voltage 3 AC 380 ... 480 V)
Article number
Type rating
Motor Modules, DC 675 ... 1035 V (line voltage 3 AC 500 ... 690 V)
Article number
Type rating
Output current
[kW]
[A]
110
210
132
260
160
310
250
490
400
745
560
985
710
1260
800
1405
Output current
[kW]
[A]
90
100
132
150
200
215
315
330
450
465
560
575
800
810
1000
1025
1200
1270
1500
1560
Motor Modules
6.6 Technical specifications
Minimum cable length
[m]
30
27
20
15
10
8
8
5
Minimum cable length
[m]
90
70
50
30
25
20
15
10
8
7
177