7 - DETAILED MENU STRUCTURE
Setpoint Table Menu – SETPOINT
No. Name
Status
1
csp1
-28.9 to 26.0
-20 to 78.8
2
csp2
-28.9 to 26.0
-20 to 78.8
3
ice_sp
-28.9 to 26.0
-20 to 78.8
4
cramp_sp
0.11 to 11.11
0.2 to 20
5
hsp1
26.7 to 63.0
80 to 145.4
6
hsp2
26.7 to 63.0
80 to 145.4
7
hramp_sp
0.11 to 11.11
0.2 to 20
8
w_sct_sp
26.67 to 48.89
80 to 120
9
lim_sp1
0 to 100
10
lim_sp2
0 to 100
11
lim_sp3
0 to 100
*Displayed in English by default.
Default Unit
Displayed text *
6.7
°C
Cooling Setpoint 1
44
°F
6.7
°C
Cooling Setpoint 2
44
°F
6.7
°C
Cooling Ice Setpoint
44
°F
0.6
^C
Cooling Ramp Loading
1
^F
37.8
°C
Heating Setpoint 1
100
°F
37.8
°C
Heating Setpoint 2
100
°F
0.6
^C
Heating Ramp Loading
1
^F
35
°C
Water Val Condensing Stp Condensing setpoint
95
°F
100
%
Switch Limit Setpoint 1
100
%
Switch Limit Setpoint 2
100
%
Switch Limit Setpoint 3
Description
Cooling setpoint 1 (used during occupied periods)
Cooling setpoint 2 (used during unoccupied periods)
Cooling ice setpoint
Cooling ramp loading setpoint (rate at which the water temperature
may change within one minute)
Heating setpoint 1 (used during occupied periods)
Heating setpoint 2 (used during unoccupied periods)
Heating ramp loading setpoint (rate at which the water temperature
may change within one minute)
Demand limit setpoint 1
Demand limit setpoint 2
Demand limit setpoint 3
21