6 - SETTING UP TOUCH PILOT CONTROL

6.13 - Schedule setting

The first timer program (schedule 1, OCCPC01S) provides a
means to automatically switch the unit from an occupied mode to
an unoccupied mode: the unit is started during occupied periods.
The second timer program (schedule 2, OCCPC02S) provides
a means to automatically switch the active setpoint from an
occupied setpoint to an unoccupied setpoint: cooling/heating
setpoint 1 is used during occupied periods and cooling/heating
setpoint 2 during unoccupied periods.
Occupancy periods
The control offers the user the possibility of setting eight occupancy
periods where each occupancy period includes the following
elements to be defined:
■ Day of the week: Select the days when the period is occupied.
■ Occupancy time ("occupied from" to "occupied to"): Set
occupancy hours for the selected days.
■ Timed Override Extension: Extend the schedule if necessary.
This parameter can be used in the case of some unplanned
events. Example: If the unit is normally scheduled to run
between 8:00 to 18:00, but one day you want the air-conditioning
system to operate longer, then set this timed override extension.
If you set the parameter to "2", then the occupancy will end at
20:00.
To set the unit start/stop schedule
1. Go to the Main menu.
2.  Navigate to the Configuration menu (logged-in users only) and 
select Schedule (SCHEDULE).
3. Go to OCCPC01S.
4. Select appropriate check boxes to set the unit occupancy on
specific days.
5.  Define the time of occupancy.
6. Then the time schedule is set, the selected period will be
presented in the form of the green band on the timeline.
7. Press the Save button to save your changes or the Cancel
button to exit the screen without making modifications.
(1)
(3) (4)
Legend
1. Selection of days for the time schedule
2. Start/end of the schedule
3. Save
4. Cancel
5. Previous time period
6. Next time period
■ Each program is in unoccupied mode unless a schedule
time period is active.
■ If two periods overlap and are both active on the same day,
then the occupied mode takes priority over the unoccupied
period.
14
Example: Schedule setting (schedule 1)
Hour
00:00
1:00
2:00
3:00
4:00
5:00
6:00
7:00
8:00
9:00
10:00
11:00
12:00
13:00
14:00
15:00
16:00
17:00
18:00
19:00
20:00
21:00
22:00
23:00
MON:
TUE:
WED:
THU:
FRI: 
SAT:
SUN:
HOL:
Period / Schedule
P1: Period 1
P2: Period 2
(2)
P3: Period 3
P4: Period 4
P5: Period 5
P6: Period 6
P7: Period 7
P8: Period 8
(5) (6)
Holidays
The control allows the user to define 16 holiday periods, where 
each period is defined by three parameters; the month, the start 
day and the duration of the holiday period.
During the holiday periods, the controller will be in occupied or
unoccupied mode, depending on the periods validated as holidays.
Each holiday period can be modified by the user via the Configuration 
menu (see section 7.2).
MON
TUE
WED
THU
FRI
P1
P1
P1
P2
P2
P3
P4
P4
P2
P2
P3
P4
P4
P2
P2
P3
P4
P4
P2
P2
P3
P4
P4
P2
P2
P3
P4
P4
P2
P2
P3
P4
P4
P2
P2
P3
P4
P4
P2
P2
P3
P4
P4
P2
P2
P3
P4
P4
P2
P2
P3
P4
P4
P2
P2
P3
P3
P3
P3
Occupied
Unoccupied
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
Holiday
Starts at
Stops at
0:00
3:00
7:00
18:00
7:00
21:00
7:00
17:00
7:00
12:00
20:00
21:00
Not used in this example
Not used in this example
SAT
SUN
HOL
P5
P5
P5
P5
P5
P6
Active on (days)
Monday
Monday + Tuesday
Wednesday
Thursday + Friday
Saturday
Holidays