7 - DETAILED MENU STRUCTURE
General Parameters Menu – GENUNIT
No. Name
Status
1
CTRL_TYP
0 to 2
2
STATUS
-
3
CHIL_S_S
disable/
enable
4
CHIL_OCC
no/yes
5
min_left
-
6
HEATCOOL
-
7
HC_SEL
cool/heat
8
SP_SEL
0 to 2
9
10
SP_OCC
no/yes
11
CAP_T
0 to 100
12
CAPA_T
0 to 100
13
CAPB_T
0 to 100
14
SP
-
15
CTRL_PNT
-
16
TOT_CURR
-
17
CURR_LIM
0 to 2000
18
EMSTOP
disable/
enable
19
DEM_LIM
0 to 100
*Displayed in English by default.
Temperatures Menu – TEMP
No. Name
Status
1
COOL_EWT
-
2
COOL_LWT
-
3
COND_EWT
-
4
COND_LWT
-
5
SPACETMP
-
6
CHWSTEMP
-
7
CHWSHEAT
-
8
DGT_A
-
9
SCT_A
-
10
LIQT_A
-
11
SLT_A
-
12
SST_A
-
13
SUCT_A
-
14
DGT_B
-
15
SCT_B
-
16
LIQT_B
-
17
SLT_B
-
18
SST_B
-
19
SUCT_B
-
*Displayed in English by default.
Default Unit
Displayed text *
0
-
Local=0 Net.=1 Remote=2 Operating mode:
-
-
Run Status
disable
-
Net.: Cmd Start/Stop
no
-
Net.: Cmd Occupied
-
min
Minutes Left for Start
-
-
Heat/Cool status
-
-
Heat/Cool Select
0
-
Setpoint Select
0=Auto. 1=Spt1. 2=Spt2
yes
-
Setpoint Occupied?
0
%
Percent Total Capacity
0
%
Circuit A Total Capacity
0
%
Circuit B Total Capacity
-
°C / °F
Current Setpoint
-
°C / °F
Control Point
-
A
Actual Chiller Current
0
A
Chiller Current Limit
disable
-
Emergency Stop
0
%
Active Demand Limit Val
Default Unit
Displayed text *
-
°C / °F
Cooler Entering Fluid
-
°C / °F
Cooler Leaving Fluid 
-
°C / °F
Condenser Entering Fluid Condenser entering water temperature: Used for capacity control
-
°C / °F
Condenser Leaving Fluid Condenser leaving water temperature: Used for capacity control
-
°C / °F
Optional Space Temp
-
°C / °F
CHWS Temperature
-
°C / °F
CHWS Heat Temp
-
°C / °F
Discharge Gas Temp cir A Discharge gas temperature, circuit A
-
°C / °F
Saturated Cond Tmp cir A Saturated condensing temperature, circuit A
-
°C / °F
SubCooling Temp cir A
-
°C / °F
Saturated Liquid temp A
-
°C / °F
Saturated Suction Temp A Saturated suction temperature, circuit A
-
°C / °F
Compressor Suction Tmp A Compressor suction temperature, circuit A
-
°C / °F
Discharge Gas Temp cir B Discharge gas temperature, circuit B
-
°C / °F
Saturated Cond Tmp cir B Saturated condensing temperature, circuit B
-
°C / °F
SubCooling Temp cir B
-
°C / °F
Saturated Liquid temp B
-
°C / °F
Saturated Suction Temp B Saturated suction temperature, circuit B
-
°C / °F
Compressor Suction Tmp B Compressor suction temperature, circuit B
Description
0 = Local; 1 = Network; 2 = Remote 
Off, Running, Stopping, Delay, Trip out, Ready, Override, etc.
Unit start/stop via Network: When the unit is in Network mode,
start/stop command can be forced
Unit time schedule via Network: When the unit is in Network mode,
the forced value can be used instead of the real occupancy state
Minutes before the unit start-up
Heating/cooling status: Heat/Cool
Heating/cooling selection
Setpoint selection
0 = Auto (schedule control)
1 = Setpoint 1
2 = Setpoint 2
Setpoint occupancy status
Total unit capacity
Total capacity, circuit A
Total capacity, circuit B
Current setpoint
Control point: Water temperature that the unit must produce
Actual chiller current
Chiller current limit
Emergency stop: Used to stop the unit regardless of its active
operating type
Active demand limit value: When the unit is in Network mode, the
minimum value will be used compared to the status of the external
limit switch contact and the demand limit switch setpoint
Description
Evaporator entering water temperature: Used for capacity control
Evaporator leaving water temperature: Used for capacity control
Optional space temperature
Master/slave temperature
Master/slave heating temperature
Subcooling temperature, circuit A
Saturated liquid temperature, circuit A
Subcooling temperature, circuit B
Saturated liquid temperature, circuit B
17