Carrier Touch Pilot Control Series Control Manual page 20

Table of Contents

Advertisement

7 - DETAILED MENU STRUCTURE
DC Free Cooling Status Menu – DCFC_STA
No. Name
Status
1
oat
-
2
lwt
-
3
wloop
-
4
m_dcfc
no / yes
5
dcfc_cap
0 to 100
6
dcfc_al
normal /
alarm
7
f_stage
0 to 10
8
vf_speed
0 to 100
9
pid_out
0 to 100
10
FC_HOUR
0 to 999999
11
FC_FAN1S
0 to 999999
12
FC_FAN1H
0 to 999999
13
FC_FAN2S
0 to 999999
14
FC_FAN2H
0 to 999999
15
FC_FAN3S
0 to 999999
16
FC_FAN3H
0 to 999999
17
FC_FAN4S
0 to 999999
18
FC_FAN4H
0 to 999999
19
FC_FAN5S
0 to 999999
20
FC_FAN5H
0 to 999999
21
FC_FAN6S
0 to 999999
22
FC_FAN6H
0 to 999999
23
FC_FAN7S
0 to 999999
24
FC_FAN7H
0 to 999999
25
FC_VFANS
0 to 999999
26
FC_VFANH
0 to 999999
*Displayed in English by default.
Air Condenser Status Menu – AIR_COND
No. Name
Status
1
oat
-
2
3
DC_LWT
-
4
DC_FanSt
-
5
DC_FanSp
-
6
7
FanSt_A
-
8
FanSp_A
-
9
FanSt_B
-
10
FanSp_B
-
11
12
COND_F1S
-
13
COND_F1H
-
14
COND_F2S
-
15
COND_F2H
-
16
COND_F3S
-
17
COND_F3H
-
18
COND_F4S
-
19
COND_F4H
-
20
COND_F5S
-
21
COND_F5H
-
22
COND_F6S
-
23
COND_F6H
-
24
COND_F7S
-
25
COND_F7H
-
26
COND_F8S
-
27
COND_F8H
-
28
CirA_VFS
-
29
CirA_VFH
-
30
CirB_VFS
-
31
CirB_VFH
-
*Displayed in English by default.
20
Default Unit
Displayed text *
-
°C / °F
OAT Free Cooling
-
°C / °F
FC Leaving Water Temp
-
°C / °F
FC Water Loop Temp
no
-
Free Cooling Mode Active Free Cooling mode active
0
%
FC Capacity
normal
-
DCFC process is in alarm Dry Cooler Free Cooling process failure
0
-
Fans Stage
0
%
Varifan Speed
0
%
PID Output
0
hour
DCFC Operating Hours
0
-
DCFC Fan Stage 1 Start DCFC / Fan stage 1: Number of starts
0
hour
DCFC Fan Stage 1 Hours DCFC / Fan stage 1: Operating hours
0
-
DCFC Fan Stage 2 Start DCFC / Fan stage 2: Number of starts
0
hour
DCFC Fan Stage 2 Hours DCFC / Fan stage 2: Operating hours
0
-
DCFC Fan Stage 3 Start DCFC / Fan stage 3: Number of starts
0
hour
DCFC Fan Stage 3 Hours DCFC / Fan stage 3: Operating hours
0
-
DCFC Fan Stage 4 Start DCFC / Fan stage 4: Number of starts
0
hour
DCFC Fan Stage 4 Hours DCFC / Fan stage 4: Operating hours
0
-
DCFC Fan Stage 5 Start DCFC / Fan stage 5: Number of starts
0
hour
DCFC Fan Stage 5 Hours DCFC / Fan stage 5: Operating hours
0
-
DCFC Fan Stage 6 Start DCFC / Fan stage 6: Number of starts
0
hour
DCFC Fan Stage 6 Hours DCFC / Fan stage 6: Operating hours
0
-
DCFC Fan Stage 7 Start DCFC / Fan stage 7: Number of starts
0
hour
DCFC Fan Stage 7 Hours DCFC / Fan stage 7: Operating hours
0
-
DCFC Variable Fan Start DCFC / Variable-speed fan: Number of starts
0
hour
DCFC Variable Fan Hours DCFC / Variable-speed fan: Operating hours
Default Unit
Displayed text *
-
°C / °F
Outdoor Air Temperature Outdoor air temperature
Dry Cooler Status
-
°C / °F
Leaving Water Temp
-
-
Runing Fan Stages
-
%
Variable Speed
Air Condensing
-
-
Circuit A Fan Stages
-
%
Variable Speed Fan A
-
-
Circuit B Fan Stages
-
%
Variable Speed Fan B
Runtime
-
-
Condensing Fan 1 Start
-
hour
Condensing Fan 1 Hours Condensing fan 1: Operating hours
-
-
Condensing Fan 2 Start
-
hour
Condensing Fan 2 Hours Condensing fan 2: Operating hours
-
-
Condensing Fan 3 Start
-
hour
Condensing Fan 3 Hours Condensing fan 3: Operating hours
-
-
Condensing Fan 4 Start
-
hour
Condensing Fan 4 Hours Condensing fan 4: Operating hours
-
-
Condensing Fan 5 Start
-
hour
Condensing Fan 5 Hours Condensing fan 5: Operating hours
-
-
Condensing Fan 6 Start
-
hour
Condensing Fan 6 Hours Condensing fan 6: Operating hours
-
-
Condensing Fan 7 Start
-
hour
Condensing Fan 7 Hours Condensing fan 7: Operating hours
-
-
Condensing Fan 8 Start
-
hour
Condensing Fan 8 Hours Condensing fan 8: Operating hours
-
-
Cond VariFan CirA Start
-
hour
Cond VariFan CirA Hour
-
-
Cond VariFan CirB Start
-
hour
Cond VariFan CirB Hour
Description
Free Cooling / Dry cooler: OAT
Free Cooling / Dry Cooler: Leaving water temperature
Free Cooling / Dry Cooler: Water loop temperature
Free Cooling / Dry Cooler capacity
Free Cooling / Dry Cooler fan stage (fix-speed fans)
Free Cooling / Dry Cooler: Fan speed (variable-speed fans)
Status of PID output
Free Cooling / Dry cooler: Operating hours
Description
Status of the Dry Cooler connected on the condenser side
Leaving water temperature
Running fan stages
Variable Speed
Status of the air condenser connected to the refrigerant circuits
Circuit A Fan Stages
Variable-speed Fan, circuit A
Circuit B Fan Stages
Variable-speed Fan, circuit B
Runtime
Condensing fan 1: Number of starts
Condensing fan 2: Number of starts
Condensing fan 3: Number of starts
Condensing fan 4: Number of starts
Condensing fan 5: Number of starts
Condensing fan 6: Number of starts
Condensing fan 7: Number of starts
Condensing fan 8: Number of starts
Condensing variable-speed fan (circuit A): Number of starts
Condensing variable-speed fan (circuit A): Operating hours
Condensing variable-speed fan (circuit B): Number of starts
Condensing variable-speed fan (circuit B): Operating hours

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

19pv 55019pv 1600

Table of Contents