Appliance Selection; Ignition Cycle; Flame Detection - Slant/Fin VHG-100-CH Installation And Service Manual

High efficiency condensing gas boiler
Table of Contents

Advertisement

A
PPLIANCE SELECTION
The control is designed to store specific parameter sets of different boiler models.
By defining specific setting for different appliance models the same control can be used for a complete product
range. Depending on which model the control is applied to, it will only be necessary to change a single parameter.
When this parameter (138) is changed, the following settings are changed:
Maximal fan speed
Minimal fan speed
*Ignition speed is the same as Pre-Purge Speed and Post Purge speed.
The following appliances are available:
APPLIANCE SELECTION (Parameter 138)
Boiler type:
80 CH
Natural gas
50
Propane
51
Not Used
Attention!
This does not apply to the external igniter BCU, see mounting instructions of that BCU.

Ignition cycle

During the ignition cycle multiple safety checks are active
False flame detection
Re-ignition
Flame establishing
time
Flame out too late
Flame loss
Fan supervision
Table 11.7
F
LAME DETECTION
When the boiler is firing, and the flame is not detected anymore, the gas valve will be closed, and the control will
perform a post-purge, after which a restart will take place.
The presence of a flame is measured through the flame rod that points into the flame. The flame current is measured
by the control as ionization in micro amps (μA).
When the flame current is above Flamerod_Setpoint plus Flamerod_Hysterese (1.0 μA plus 0.5 μA) a flame will be
present. When the flame current is below Flamerod_Setpoint (1.0 μA) the flame will not be present.
96
100 CH
120 CH
52
54
53
55
x
If flame is detected at the end of the pre-spark period (Pre-ignite) a lockout error
occurs.
If at the end of the safety period, no flame is detected, the control will go to post-purge
in order to remove the unburned gas. After this a re-ignition attempt is started
following the same cycle.
The number of re-ignition attempts is limited to Max_Ignit_Trials after which a lockout
occurs.
Sparking stops in the Flame Proving state to allow for ionization detection.
The Flame Proving state takes Safety_Period - Ignit_Period.
If at the end of the Post purge 0 state, the flame is still detected a lockout follows.
When a flame is lost during a burn cycle the control will restart the boiler once. At the
second flame loss the boiler will stop and blocking mode follows. The number of
restarts is limited by the Max_Flame_Trials setting. (Default set to 1)
The fan speed is continuously monitored.
E93.1901EN032 Installation and Service Manual SlantFin VGH-CH / CO
Ignition speed*
Maximum flue gas temperature
150 CH
180 CH
90 CO
50
52
51
53
54 - 55
52-55
150 CO
200 CO
50
50
50
51
51
51
52-55
52-55
Table 11.6
Figure 11.5