Menu Structure Display - Slant/Fin VHG-100-CH Installation And Service Manual

High efficiency condensing gas boiler
Table of Contents

Advertisement

Menu structure display

Menu structure Display:
1. Central Heating (CH)
2. Domestic Hot Water (DHW)
3. Information
4. Settings
5. System Test
1. Central Heating (CH)
1.1 CH Setpoint
1.2 Outdoor Reset
1.2 Outdoor reset
Design Supply T.
Base Supply T.
WW Shutdown
Bas. Outd. T.
Des. Outd. T.
2. Domestic Hot Water
(DHW)
DHW Setpoint
DHW Store Setpoint
3. Information
3.1 Software versions
3.2 Boiler Status
3.3 Boiler History
3.4 Error Log
3.5 Service
3.1 Software versions
Display
Boiler
Device Group
106
min.
max.
Default
68
194
176
(20)
(90)
(80)
min.
max.
Default
68
194
176
(20)
(90)
(80)
68
194
104
(20)
(90)
(40)
32
95
72
(0)
(35)
(22)
32
86
68
(0)
(30)
(20)
-13
77
23
(-25)
(25)
(-5)
min.
max.
Default
104
160
122
(40)
(71)
(50)
104
160
122
(40)
(71)
(50)
min.
max.
Default
min.
max.
Default
E93.1901EN032 Installation and Service Manual SlantFin VGH-CH / CO
Access
Description:
level
User
Enter the Central Heating (CH)
menu
User
Enter the Domestic Hot Water
(DHW) menu
User
Enter the Information menu
User
Enter the Settings menu
User
Enter the System Test menu
(see chapter 15).
unit
Access
Description:
level
°F
Installer
Set the CH setpoint if CH mode is 0
(°C)
User
Enter the Outdoor Reset menu if
CH mode is 1
unit
Access
Description:
level
°F
Installer
Set CH setpoint when outdoor
(°C)
temperature equals Des. Outd. T.
°F
Installer
Set CH setpoint when outdoor
(°C)
temperature equals Bas. Outd. T.
°F
Installer
Set outdoor temperature above
(°C)
which CH demand is locked.
°F
Installer
Set the outdoor temperature at
(°C)
which CH setpoint is set to Bas.
Supply T.
°F
Installer
Set the outdoor temperature at
(°C)
which CH setpoint is set to Des.
Supply T.
unit
Access
Description:
level
°F
Installer
Set the DHW setpoint
(°C)
°F
Installer
Set the DHW store setpoint for
(°C)
DHW mode 1 and 2
unit
Access
Description:
level
User
Enter the Software Versions menu
User
Enter the Boiler Status menu
User
Enter the Boiler History menu
User
Enter the Error Log menu
User
Enter the Service menu
unit
Access
Description:
level
xxxx
User
Display the software checksum
xxxx
xxxx
User
Display the boiler software checksum
xxxx
xxxMN
User
Display the boiler group ID