NSTRUCTIONS FOR WORKING WITH CEMENTING
1. Work from boiler to vent or air termination. Do not exceed lengths given in this manual for the air or vent piping.
2. Cut pipe to the required lengths and deburr the inside and outside of the pipe ends.
3. Chamfer outside of each pipe end to ensure even cement distribution when joining.
4. Clean all pipe ends and fittings using a clean dry rag (moisture will retard curing and dirt or grease will prevent
adhesion).
5. Dry fit vent or air piping to ensure proper fit up before assembling any joint. The pipe must go a third to two-
thirds into the fitting to ensure proper sealing after cement is applied.
6. Priming and Cementing:
a. Handle fittings and pipes carefully to prevent contamination of surfaces.
b. Apply a liberal even coat of primer to the fitting socket and to the pipe end to approximately 1/2" beyond
the socket depth.
c. Apply a second primer coat to the fitting socket.
d. While primer is still wet, apply an even coat of approved cement to the pipe equal to the depth of the fitting
socket along with an even coat of approved cement to the fitting socket.
e. Apply a second coat of cement to the pipe.
f.
While the cement is still wet, insert the pipe into the fitting, if possible, twist the pipe a 1/4 turn as you insert
it. Note: If voids are present, sufficient cement was not applied and joint could be defective.
g. Wipe excess cement from the joint removing ring or beads as it will needlessly soften the pipe.

Polypropylene

This product has been approved for use with polypropylene vent with the manufacturers listed.
All terminations must comply with listed options in this manual and be a single-wall vent offering.
For support and special connections required, see the manufacturer's instructions.
All vent is to conform to standard diameter and equivalent length requirements established.
Approved polypropylene vent pipe and fittings.
Supplier
Type
Duravent
PolyPro
Centrotherm
InnoFlue
Table 9.7
Approved polypropylene terminations:
Duravent – PolyPro
Boiler
VGH-80-CH / VGH-90-CO
VGH-100-CH / VGH-120-CH
VGH-150-CO / VGH-150-CH
VGH-180-CH / VGH-200-CO
Table 9.8
Safety authorities in some jurisdictions are not allowing PVC venting materials with
appliances of any kind, even if System 636 certified. Check with the local safety inspector
to verify compliance. Canadian installations must comply with the current CSA B149.1
Installation Code and local building codes.
In Canada, CPVC and PVC vent pipe, fittings and cement/ primer must be ULC-S636
certified.
Use only cleaners, primers, and solvents that are approved for the materials which are
joined together.
All PVC vent pipes must be glued, properly supported, and the exhaust must be pitched a
minimum of a 1/4 inch per foot back to the boiler (to allow drainage of condensate).
Termination
Twin Pipe Side Wall
Single Pipe Side Wall stainless
Bird Screen
concentric roof
concentric wall
E93.1901EN032 Installation and Service Manual SlantFin VGH-CH / CO
PVC/ CPVC
PIPE CONNECTIONS
Color
2" Order
black
2PPS-HTPL
2PPS-HSTL
stainless
2PPS-BG
black
2PPS-VKL
terra-cotta
2PPS-VK-TCL
white
2PPS-HKL
2" Stock
3" Order
810009685 3PPS-HTPL
810009684 3PPS-HSTL
810004341 3PPS-BG
810009692 3PPS-VKL
810009693 3PPS-VK-TCL 810009721
810009682 3PPS-HKL
3" Stock
810009713
810009712
810004355
810009720
810009710
55

Advertisement

Table of Contents
loading

Table of Contents