Lockout codes

Lock
Error
out
code
0
E2PROM_READ
_ERROR
1
IGNIT_ERROR
2
GV_RELAY_
ERROR
3
SAFETY_RELAY
_ERROR
4
BLOCKING_
TOO_LONG
5
FAN_ERROR_
NOT_RUNNING
6
FAN_ERROR_
TOO_SLOW
7
FAN_ERROR_
TOO_FAST
8
RAM_ERROR
9
WRONG_
EEPROM_
SIGNATURE
10
E2PROM_
ERROR
11
STATE_ERROR
12
ROM_ERROR
13
APS_NOT_
OPEN
14
APS_NOT_
CLOSED_IN_
PRE_ PURGE
15
MAX_TEMP_
ERROR
114
Description
Internal software error
Five unsuccessful ignition
attempts in a row
Failure detected in the
gas valve relay
Failure detected in safety
relay
Control had a blocking
error more than 20 hours
Fan is not running for
more than 60 seconds
Fan runs too slow for
more than 60 seconds
Fan runs too fast for more
than 60 seconds
Internal software error
Contents of E2prom is not
up to date
Wrong safety parameters
in E2prom
Internal software error
Internal software error
Air pressure switch not
opening during pre-purge
0
Air pressure switch not
closing during pre-purge 1
The external overheat
protection is enabled or
the T_Supply sensor
measures a temp. of over
Prot_Overheat_Temp -
SGOverheat_Duplex_Tol
erance for a period of
Max_Value_Period
E93.1901EN032 Installation and Service Manual SlantFin VGH-CH / CO
Cause
wrongly programmed
BCU or PB
no gas, wrongly
adjusted gas valve
short circuit in coil of
the gas valve, water
on wiring or gas valve
safety relay is not
working correctly
blocking code active
more than 20 hours
electrical wiring not
correctly connected,
or fan malfunctioning
electrical wiring not
correctly connected,
or fan malfunctioning
electrical wiring not
correctly connected,
or fan malfunctioning
wrongly programmed
BCU or PB
outdated E2prom
wrongly programmed
BCU or PB
wrongly programmed
BCU or PB
wrongly programmed
BCU or PB
electrical circuit is
short circuited, or
APS is jammed
no air transport to the
burner; flue or air
inlet is blocked, or
APS is jammed, or
air signal hose not
connected to the air
intake pipe or water
in hose
burner door clixon
tripped because of
overheating of the
burner door or the
water flow is
restricted, or back
wall thermal fuse has
tripped because rear
wall insulation disc
(combustion
chamber) is
damaged or broken.
Solving
reset BCU or replace BCU
and or display unit
check gas supply and ad-
just gas valve, reset BCU
reset BCU replace gas
valve or wiring harness
reset BCU or replace BCU
reset and check blocking
code
check wiring or replace Fan
if not solved check fuse on
BCU or replace BCU
check wiring or replace Fan
if not solved check fuse on
BCU or replace BCU
check wiring or replace Fan
if not solved check fuse on
BCU or replace BCU
reset BCU or replace BCU
and or display unit
reset BCU or replace BCU
reset BCU or replace BCU
reset BCU or replace BCU
reset BCU or replace BCU
check wiring or replace
APS
check if there are any
obstructions in the flue or
air intake, replace APS if
jammed, connect air hose
to the air intake pipe,
remove any water from the
hose.
check burner door gasket
and replace burner door
gasket and reset clixon on
burner door or check
circulator and waterflow
and replace circulator or
increase water flow check
also if valves are closed or
check if rear wall fuse is
broken if so replace and
also replace rear wall
insulation disc (combustion
chamber).