Building Technologies
Fire Safety
1
Cable tree to periphery board or fire terminal board
2
Existing cable tree (connection for master power supply)
3
Additional cable tree for the second power supply (slave)
4
Additional fused terminal (F2) on the DIN rail
●
The connection lines marked in bold of the additional cable tree (3) and the
existing cable tree (2) must be wired again when installing the second power
supply (slave).
●
In order to avoid operating temperature differences, the two power supply units
must be mounted next to each other in the same housing.
●
The batteries and the system supply must only be connected to the master
power supply unit.
●
The positive pole for the batteries must be unwired at connection X8-9 (Master)
and be provided with an external fuse.
●
Only one temperature sensor must be connected to the master power supply
unit.
●
The temperature sensor must be fitted close to the batteries. (You will find
precise details in document A6V10210390).
Installing, exchanging and connecting modules
Power supply (150 W)
6
79 | 222
A6V10210390_j_en_--
2015-12-15