6.3 Periphery board (4 loops)
6.3.1 Installation
X400
X401
1
Building Technologies
Fire Safety
The periphery board (4-loop) FCI2004-A1 is already mounted in the fire control
panels in the factory and only has to be replaced in the event of a repair.
Prerequisites
●
Components that make access to the periphery board difficult are removed
(e.g. mounting plate).
●
All connections and plug connectors are disconnected (label cables before
disconnecting them).
●
The periphery board is removed.
X5
X7
X22
X6
X8
X3
X1
Figure 25: Mounting of the periphery board (4 loops)
1
Threaded bolts on rear panel
2
13 fixing screws
3
Periphery board (4 loops)
X3
Connector for connection cable to PMI & mainboard (operating unit)
X400 Connector for the periphery bus to the fire brigade periphery module [DE]
X401 Connector for periphery bus
Installing, exchanging and connecting modules
X11
X21
X12
2
3
Periphery board (4 loops)
A6V10210390_j_en_--
2015-12-15
6