Installing, exchanging and connecting modules
6
Input/output module FDCIO224 [DE]
6.22.2 Pin assignments
6.23 Input/output module FDCIO224 [DE]
6.23.1 Installation
172 | 222
Building Technologies
Fire Safety
The pin assignment of the Redux module is listed in the manual of the Redux
module.
During connection please observe the following:
●
The data cables of the Redux module are connected to the RS485 interface.
●
The supply of the Redux module is connected to the periphery board.
–
Periphery board (2 loops) FCI2002-A1: Supply output 2 on plug X9
–
Periphery board (4 loops) FCI2004-A1: Supply output 1 on plug X8
●
The fault output of the Redux module can be connected to any I/O on the
periphery board. The I/O must be configured accordingly.
The input/output module FDCIO224 has four potential-free contact inputs and four
control outputs for VdS-compliant connection of the VdS extinguishing interface.
For this application it must be installed in the fire control panel. The input/output
module is mounted onto the DIN rail.
2
1
Figure 100: Installing the input/output module FDCIO224 in the fire control panel
1
Input/output module FDCIO224
2
DIN rail
3
Mounting feet
1. Insert the two mounting feet (3) at the sides of the input/output module.
2. Push the input/output module (1) with the mounting feet (3) against the DIN rail
(2) until the mounting feet snap into place.
3. Connect the input/output module according to the pin assignment. You will find
the pin assignment in document 007023, Technical Manual.
1
3
2