3. WATER TREATMENT

Before and during assembly, the system must be kept free
of impurities, construction dust, sand, copper dust, grease,
carbon deposits, etc., as well as welding flux residue. In
any of these instances, the old system must be rinsed with
clear water mixed with a highly concentrated rinse agent.
More generally, it is advised to implement any procedure
necessary to prevent or treat contamination.
Black oxide sludge (magnetite-Fe
continuous electrolytic corrosion in any system unprotected
by an inhibitor. Iron oxide (Fe
produced during oxygenation. Scale deposit is made
up of lime scale contained in most distributed water that
settles over the warmest surfaces of the system. Sludge
and scale do mix together and are the cause of the main
encountered field problems on heating installations.
The presence of these substances means that standard
precautions are not implemented. In this case, product
warranty cannot be applied.
The chemical compatibilitiy of several products for the
treatment of heating water equipment has been tested on
heat exchangers.
Raypak recommends the using of these corrosion inhibitors
in preventive and curative treatment for boilers.
INLET
PLUMBING
O
) forms as a result of
3
4
O
) (red oxide sludge) is
2
3
Producers
Fernox
Inhibitors
Protector
F1 / Alphi 11
Noise
reducer
Universal
Restorer
Cleaner
Sludge
Protector F1
remover
Cleaner F3
Antifreeze
Alphi 11
Table B.
Corrosion/Scale Inhibitors and Recommended
Suppliers
Treatment Type
Preventitive
Protector F1
Cleaner F3
X100
X200
X300
X400
X500
Alphi 11
Sotin 212
MC1+
Table C.
Treatment Type
Water Chemistry
Water Temperature
pH (system contains aluminum parts)
pH (without aluminum parts)
Total Dissolved Solids (GPG)
Table D.
Boiler Water Chemistry
Water Hardness
Models
4-12 GPG
WH7-300B
27.3GPM
WH7-400B
27.3GPM
WH7-500B
32.8GPM
WH7-650B
43.7GPM
WH7-800B
54.6GPM
WH7-1000B
65.5GPM
* When water hardness is higher than 15 GPG, a softener shall be
used. Water hardness values for calcium carbonate.
Table E.
Water Heater Minimum Flow Rate
Sentinel
Sotin
ADEY
X100,
Sotin
MC1+
X500
212
X200
X300
X400
Sotin
212
X500
Curative
X
X
X
X
X
X
X
X
X
X
X
Boiler
41 to 212°F
7.5-8.5
7.5-9.5
3-9
Water Hardness
PH
12-15 GPG*
36.7GPM
36.7GPM
44GPM
6.0-8.5
58.6GPM
73.3GPM
88.0GPM
7