Vent Terminal Location - Raypak Xfiire 300B Installation And Operation Manual

Table of Contents

Advertisement

Vent Terminal Location

NOTE: During winter months check the vent cap and
make sure no blockage occurs from build-up of snow
or ice.
1. Condensate can freeze on the vent cap. Frozen
condensate on the vent cap can result in a blocked
flue condition.
2. Give special attention to the location of the vent
termination to avoid possibility of property damage
or personal injury.
3. Gases may form a white vapor plume in winter. The
plume could obstruct a window view if the termination
is installed near windows.
4. Prevailing winds, in combination with below-freezing
temperatures, can cause freezing of condensate and
water/ice build-up on buildings, plants or roofs.
5. The bottom of the vent terminal and the air intake
shall be located at least 12" (305 mm) above grade,
including normal snow line.
6. Un-insulated single-wall Category IV metal vent
pipe shall not be used outdoors in cold climates for
venting gas-fired equipment without insulation.
7. Through-the-wall vents for Category IV appliances
shall not terminate over public walkways or over
an area where condensate or vapor could create
a nuisance or hazard or could be detrimental to
the operation of regulators, relief valves, or other
equipment.
8. Locate and guard vent termination to prevent
accidental contact by people or pets.
9. DO NOT terminate vent in window well, stairwell,
alcove, courtyard or other recessed area.
10. DO NOT terminate above any door, window, or
gravity air intake. Condensate can freeze, causing
ice formations.
11. Locate or guard vent to prevent condensate from
damaging exterior finishes. Use a rust-resistant
sheet metal backing plate against brick or masonry
surfaces.
12. DO NOT extend exposed vent pipe outside of
building beyond the minimum distance required for
the vent termination. Condensate could freeze and
block vent pipe.
U.S. Installations
Refer to the latest edition of the National Fuel Gas Code.
Vent termination requirements are as follows:
1. Vent must terminate at least 4' (1.2 m) below or 4'
(1.2 m) horizontally from, window or gravity air inlet
to the building.
2. The vent must not terminate above public walkways
due to slip hazard from frozen condensate.
3. Terminate vent at least 3' (915 mm) above any forced
air inlet located within 10' (3 m).
4. Vent must terminate at least 4' (1.2 m) horizontally,
and in no case above or below unless 4' (1.2 m)
horizontal distance is maintained, from electric
meters, gas meters, regulators, and relief equipment.
5. Terminate vent at least 6' (1.8 m) away from adjacent
walls.
6. DO NOT terminate vent closer than 5' (1.5 m) below
roof overhang.
7. The vent terminal requires a 12" (305 mm) vent
terminal clearance from the wall.
8. Terminate vent at least 1' (305 mm) above grade,
including normal snow line.
9. Multiple direct-vent installations require a 4' (1.2 m)
clearance between the ends of vent caps located on
the same horizontal plane.
A
WARNING: The Commonwealth of Massachusetts
requires that sidewall vented heaters, installed in every
dwelling, building or structure used in whole or in part
for residential purposes, be installed using special
provisions as outlined on page 66 of this manual.
Canadian Installations
Refer to latest edition of the B149 Installation Code.
A vent shall not terminate:
1. Directly above a paved sidewalk or driveway.
2. Within 6' (1.8 m) of a mechanical air supply inlet to
any building.
3. Above a meter/regulator assembly within 3' (915 mm)
horizontally of the vertical centre-line of the regulator.
4. Within 6' (1.8 m) of any gas service regulator vent
outlet.
5. Less than 1' (305 mm) above grade level.
6. Within 3' (915 mm) of a window or door which can
be opened in any building, any non-mechanical air
supply inlet to any building or the combustion air inlet
of any other appliance.
7. Underneath a verandah, porch or deck, unless the
verandah, porch or deck is fully open on a minimum
of two sides beneath the floor, and the distance
between the top of the vent termination and the
underside of the verandah, porch or deck is greater
than 1' (305 mm).
31

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents