8. OPERATION

Lighting Instructions

1. Before operation, make sure you have read all of the
safety information in this manual.
2. Remove front panel.
3. Set the thermostat to the lowest setting.
4. Turn off all electrical power to the appliance.
5. This appliance is equipped with an ignition device
which automatically lights the burner. Do not try to
light the burner by hand.
6. Turn on main manual gas valve field-installed near
gas inlet connection on back of heater.
7. Turn on all electrical power to the appliance.
8. Set thermostat to desired setting. The appliance
will operate. The igniter will glow after the pre-
purge time delay (15 seconds). After igniter reaches
temperature (30 seconds) the main valve should
open for a 4-scond trial for ignition. System will try
for ignition up to three times (one time on optional
single-try ignition module). If flame is not sensed,
lockout will commence.
9. If the appliance will not operate, follow the instructions
"To Turn Off Gas To Appliance," and call your service
technician or gas supplier.
10. Replace front panel.
11. If heater fails to start, verify the following:
a. There are no loose connections or that the
service switch is off or in the powered, but
disabled position.
b. High temperature limit switch (optional) is set
above water temperature or manual reset high
limit is not tripped.
c. Enable/Disable circuit is closed.
d. Gas is on at the meter and the heater.
e. Incoming dynamic gas pressure to the gas
valve is NOT less than 4" WC for natural gas or
propane gas.

To Turn Off Gas To Appliance

1. Shut off manual gas valve field installed near gas
inlet connection on back of heater.
2. Remove front panel.
3. Move 3-position rocker switch to "OFF" position.
4. Turn off all electrical power to the appliance if service
is to be performed.
5. Replace access panel.
60
Heater Status Light
The light operation status of the heater change as follows:
White [Solid] - IDLE - Unit is powered on
Blue [Pulsing] - PREPURGE/IGNITION - Call for heat
Blue [Solid] - MODULATING - Burner is on
White [Pulsing] - PREPURGE - Call for heat terminated
Red [Pulsing] - ERROR - Operation error message
displayed in touchscreen.
For error details please refer to the VERSA IC control
manual (5000.72).
Figure 63. Touchscreen Illumination Key Screen

9. TROUBLESHOOTING

XFiire Error Codes

If any of the sensors detect an abnormal condition or an
internal component fails during the operation of the XFiire,
the display may show the error. This code may either
be the result of a temporary condition in which case the
display will revert to its normal readout when the condition
is corrected, or it may be the result of a condition that the
controller has evaluated as not safe to restart the unit.
In this case, the unit control will be locked out, requiring
the maintenance person to manually reset the control by
pressing and releasing the button.
Error messages are displayed in touchscreen. For
additional error details please refer to the VERSA IC
control manual (5000.72).

Heater Errors

When an error condition occurs, the controller will display
an error code on the touch screen display. These error
codes and several suggested corrective actions are
included in the XFiire Fault Text section on the following
page.

Heater Faults

1. When a fault condition occurs, the controller will flash
a red light on the PIM and display the error code on the
user interface. The alarm output will also be activated.
Most fault conditions will also cause the heater pump
to run in an attempt to cool the unit.