Raypak Xfiire 300B Installation And Operation Manual page 51

Table of Contents

Advertisement

Boiler Menu
The Boiler Menu displays various items regarding ignition, temperature monitoring, and modulation rates. As well as
software and hardware information. Up to 15 error codes can be reviewed in the Boiler Menu.
Item
Heater 1
Heater 2
Heater 3
Heater 4
IGNITION
VENT WALL
LIMIT TEMP
EMS Vdc
FIRE RATE
SPEEDX 1000
OUTLET MAX
OPERATOR
DIFF
Pump Post
FLAME CUR
MASS
IDENTITY
IGN TYPE
ID CARD
SW ID
ERROR CODE
MIN MOD ADJUST
Application
ALL
Displays Boiler for operation
CASCADE
Displays Boiler 2 for cascade operation
CASCADE
Displays Boiler 3 for cascade operation
CASCADE
Displays Boiler 4 for cascade operation
IDLE=no CFH;
PREP=pre-purge or inter-purge between trials for ignition;
IGN=trial for ignition;
BURN=burner operating;
POST=post purge;
HARD=a hard lockout fault has occurred requiring manual reset (Ignition
ALL
Lockout or manual high limit); and
SOFT=a soft lockout fault has occurred which interrupts the heating cycle
(any safety other than ignition or manual high limit)
The CFH will resume after the soft lockout fault has been corrected and a
15 min. waiting period has expired
Monitors vent temperature and adjust firing rate if vent temperature
ALL
approaches limit for vent material installed/selected
ALL
Current Outlet-Limit temperature
ALL
Current EMS signal in Volts DC
ALL
PIM firing rate
ALL
Blower speed in revolutions per minute (rpm) x 1000
Defines Max Outlet temperature offset above Target Setpoint (Press
H Mode 1, 2, 3
and hold up and down arrows for 3 seconds to enable adjustment). see
VERSA IC Manual (5000.72)
ALL
Operator Potentiometer setting on PIM
ALL
Current auto differential – Fixed by PIM
ALL
Sets the length of the heater pump purge
ALL
Flame current in micro-amps (µA)
ALL
Thermal mass recovery see VERSA IC Manual (5000.72)
ALL
Identifies the unit as heater, water heater or pool heater
ALL
PIM Board type
ALL
Identifies Raypak Identity Card
ALL
PIM Software identification number
ALL
Current Error Message
ALL
Overrides PIM Low Fire Mod value up to 60%
Table X.
Description
Boiler Menu
51

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents