Data Display Mode; Data Entry Using The Rs-232 Interface; Accessing And Leaving The Menu - Siemens SITRANS F FUH1010 Series Operating Instructions Manual

Nema 7 compact interface detector
Table of Contents

Advertisement

Section 1

Data Display Mode

After you complete the installation, and the meter is operating normally, you can use <CTRL
+ L> on your PC keyboard to toggle between Installation Menu mode and Data Display mode
(strike <L> while holding down <CTRL> key). Note that the 1010BX RS-232 interface does not
support graphics. Therefore, if you use HyperTerminal™ to view the data display screens,
you will see the data in alphanumeric form only. You can use the PC's <Up Arrow> and <Down
Arrow> to switch between available display screens.

1.12.4 DATA ENTRY USING THE RS-232 INTERFACE

The following is a step-by-step example of how to enter data for a Single-Channel 1010BX
Interface Detector using the RS-232 interface and a communications program. Most menu
cells contain default parameters. You need only access the menu cells that control a needed
parameter, such as the pipe outer diameter.

Accessing and Leaving the Menu

Make sure the Menu Lockout Switch is in the correct position. Connect the serial interface
cable between the flow computer and your laptop computer.
Run HyperTerminal™ (or your choice of communication program) using settings explained
previously.
In Command Mode, type [menu 1000]; press <ENT> to select the top level of the Installa-
tion Menu.
NOTE: The first time you access the Installation Menu, you can leave it only by saving
a site or by turning the meter off. After installing and activating a site, use
<CTRL + L> to toggle between a display screen and the last accessed menu
location.
Note on the screen above that there are two columns, a left-hand and a right-hand side. The
first left-hand item, [Meter Type], is highlighted (reversed). [Meter Type] allows you to choose
a configuration from the right-hand column list (on Single Channel models, there is only a
single channel). The next left-hand selection is Meter Facilities. Use this menu to set global
options and controls. Below [Meter Facilities] is [Using the Menu] and it explains how to
navigate through the menu. (Note: This applies only to models with an integral keypad.)
Controlotron
Site
Select Meter Type
Meter Type
Single Channel
Meter Facilities
Liquid Class
1-22
[1]
Channel 1
1010BXFM-3