Returning from alarm [A]

When an alarm occurs, remove its cause, check that the operation signal is not being inputted, ensure safety,
and reset the alarm before restarting the operation.
Remove the cause of the alarm in accordance with the following manual.
MR-J5 User's Manual (Troubleshooting)
The following table shows how to deactivate the alarm.
Alarm deactivation
Alarm reset
Power cycling

Returning from warning

Remove the cause of the warning in accordance with the following manual.
MR-J5 User's Manual (Troubleshooting)
Except for some warnings, when the cause of the warning is removed, the servo amplifier automatically returns to normal.
Warnings of the specific No. can be released with the operation alarm reset, after removing the cause.
Explanation
• Error reset command from the controller
• Click "Occurred Alarm Reset" in the "Alarm Display" window of MR Configurator2.
• Turn on RES (Reset) with an input device
• Push the "SET" button while the display of the servo amplifier is in the current alarm display mode
• Cycle the power.
• Perform the software reset with commands from the controller and MR Configurator2.
3 BASIC FUNCTION
95
3.12 Alarm function