8 - Default parameters

Ekip DIP default parameters The Ekip Dip releases are supplied with the following default parameters, some adjustable with
54 | © 2013 ABB | 1SDH001000R0002 - L7804
the front DIPs (protections, Frequency, Neutral), other via front bus (Can, modules).
Protection/Parameter
L
S
(1)
I
G
(1)
Frequency
Neutral
Hardware trip
Monitor Time
Local bus
Alive LED
(1)
Protection S available with LSI and LSIG versions of the release. Protection G available with LSIG version.
Value
1 In; 144 s
Off; 0.1 s
4 In
Off; 0.1 s
50 Hz
Off (for 3P circuit-breaker).
50% (for 4P circuit-breaker)
Disabled
5 min
Disabled
Disabled (Power LED on fixed)