Altitude The circuit breaker maintains its rated operating characteristics up to 2000 meters above sea
Electromagnetic compatibility The use of specific devices in industrial installations may cause electromagnetic interference
Storage Environment Store the circuit breaker in a dry, dust-free environment free of harsh chemicals.
23 | © 2013 ABB | 1SDH001000R0002 - L7804
level.
Once this altitude is passed, you need to consider reduction of dielectric strength and reduced
cooling capacity of the air.
The following are the corrections expressed as a percentage to be applied to the parameters
according to altitude:
Altitude (m.)
Rated service voltage (V) Ue
Rated current (A) at 40°C
in the electrical system.
The SACE Emax 2 circuit-breakers were developed and tested in an EMC environment in
accordance with IEC 60947-2, Annex J and F.
The storage ambient temperature must be:
• Circuit-breaker in the original packaging, without protection release or Ekip Dip release,
between -40 ° C and + 85 ° C.
• Circuit-breaker in the original packaging, with Ekip Touch protection release, between
-30°C and + 85°C.
NOTE: The storage conditions may differ from the usage conditions.
2000
3000
4000
100%
88%
78%
100%
98%
93%
Emax E2.2-E4.2-E6.2 circuit-breakers | 5 - Environmental conditions
ABB | SACE Emax 2
5000
68%
90%