Default Parameters - ABB Sace Emax 2 Installation, Operation And Maintenance Instructions

Emax e1.2 low voltage air circuit-breakers
Table of Contents

Advertisement

5 - Default parameters

Ekip Dip default parameters The Ekip Dip trip units are supplied with the following default parameters, some adjustable with the front
39 | © 2022 ABB | 1SDH000999R0002 - ECN000297030
Continued from the previous page
HELP
Some LED signals indicate connection errors or operational errors that require corrective or maintenance
operations. The following are the suggestions for checking with reference to the preceding LED table:
HELP note
Operation
A
Contact ABB and give details about the state of the LEDs on the unit.
Check the connections between trip unit and accessories (Rating Plug, trip
B
coil, sensors, etc).
C
Normal operation/signalling provided by the trip unit.
Error in setting of the dip-switches. Check and correct the following
conditions:
• I1 ≥ I2 or I2 ≥ I3.
• Iu < (2 * In * I1) in the case where InN = 200 %.
D
• I4 < 0.3 In (con In = 100 A), 0.25 In (con In = 400 A) or 0.2 In (for all other
sizes), in the absence of auxiliary power supply.
• t2 > 0.4s (in the case of UL circuit-breaker)
• t4 > 0.4s (in the case of UL circuit-breaker)
• I4 > 1200 A (in case of UL circuit-breaker)
E
Install by pressing and holding the itest pushbutton for at least 5s.
Connect via Ekip Connect in order to set the Local Bus or to confirm
F
maintenance.
G
Replace the battery.
DIPs (protections, Frequency, Neutral), other via front bus.
Protection/Parameter
L
S
(1)
I
G
(1)
Frequency
Neutral
Hardware Trip
Local Bus
LED Alive
Maintenance
S Protection available with LSI and LSIG versions of the trip unit. G Protection available with LSIG
(1)
version.
Value
1 In; 144 s
Off; 0.1 s
4 In
Off; 0.1 s
50 Hz (IEC) / 60 Hz (UL)
Off (for three-pole circuit breakers).
50 % (for four-pole circuit-breaker)
Disabled
Off
Disabled (Power-on LED fixed)
Off
5 - Default parameters
ABB | SACE Emax 2
Ekip Dip

Advertisement

Table of Contents
loading

Table of Contents