8 - Additional functions

Additional functions Ekip T&P, Ekip Programming and Ekip Bluetooth allow the Trip unit to be connected to Ekip Connect software

9 - Default parameters

Ekip Dip default parameters The Ekip Dip trip units are supplied with the following default parameters, some adjustable with the front DIPs
47 | © 2019 ABB | 1SDH001000R0002 - ECN000109166 - Rev. D
and to access parameters and commands that are not directly available from the front interface; the main
ones are:
Name
Description
Function allowing the user to be informed that more than a year has passed
Maintenance
since the last maintenance or that contact wear has increased by more than
10%
Bus activation so as to communicate with Ekip Link, Ekip Multimeter or Ekip
Local Bus
Signalling 10K modules
Programmable states for monitoring events, to associate with the Ekip
Programmable states
Signalling 10K contacts
Commands which activate according to the state of signals or events
Programmable Functions
programmable by the user
Led Alive
Configuration of the Power led of the Trip unit and of all modules connected
Details of these and other parameters are given in manual 1SDH001330R1002.
(protections, Frequency, Neutral), other via front bus.
Protection/Parameter
L
S
(1)
I
G
(1)
Frequency
Neutral
Hardware Trip
Local Bus
Alive LED
Maintenance
(1)
S Protection available with LSI and LSIG versions of the trip unit. G Protection available with LSIG version.
Value
1 In; 144 s
Off; 0.1 s
4 In
Off; 0.1 s
50 Hz (IEC) / 60 Hz (UL)
Off (for three-pole circuit breakers).
50 % (for four-pole circuit-breaker)
Disabled
Off
Disabled (Power-on LED fixed)
Off
Ekip Dip | 8 - Additional functions