16.1.5
Information displayed on the device monitor screen and key functions
■1. Device monitor screen
The information displayed on the device monitor screen is described below.
(6)
(7)
No.
1)
Device name
2)
Device No.
Bit device ON/OFF
3)
Timer/Counter contact ON/OFF
4)
Data type
Present value of word device
Present value and set value of timer/
5)
*1
counter
6)
Counting method
7)
Reset coil ON/OFF
8)
N/W
9)
ST
10)
CPU No.
16 - 4
16.1 Device Monitor Function
(1)
(2)
(4)
(3)
(8)
Item
Displays the device name.
Displays the device number.
Displays ON/OFF information of bit devices and timer/counter contacts
DW : Indicates that the device value is a 32-bit (two-word) module.
Nothing displayed: Indicates that the device value is a 16-bit (one-word) module.
[Decimal number]
16-bit (one-word) module: Six digits (including a digit for a sign) are displayed.
(Display example: -12345)
32-bit (two-word) module: Ten digits (including a digit for a sign) are displayed.
(Display example: -123456789)
[Hexadecimal number]
16-bit (one-word) module: Four digits are displayed. (Display example: H AB12)
32-bit (two-word) module: Eight digits are displayed. (Display example: H ABCDE123)
Displays the counting method when registering the counters from C200 to C255.
UP: Up count mode
Displays the reset coil state when registering the timer/counter for the FXCPU.
Sets or displays the network No. when the PLC is on the network.
Sets or displays the station No. when the station No. is assigned to the PLC.
0 to 4: This item must be set only when the GOT is connected to the Q series CPU in
the multiple CPU system or QnUCPU.
Changing the CPU No. cancels the registration for all the devices.
➠
16.1.7 Device registration
(5)
(9)
(10)
: ON
: OFF
DOWN: Down count mode
: ON
: OFF
Settings