Adapt The Default Setting Of The Inputs And Outputs; Advanced Commissioning - Siemens SINAMICS G110M Operating Instructions Manual

Distributed converter for simogear geared motors
Hide thumbs Also See for SINAMICS G110M:
Table of Contents

Advertisement

Figure 6-2
The abbreviations S1 ... S5b to identify the converter states are defined in the PROFIdrive
profile.
Converter
status
S1
S2
S3
S4
S51
S52
6.2.2

Adapt the default setting of the inputs and outputs

This chapter describes how you adapt the function of individual digital and analog inputs and
outputs of the inverter.
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 06/2016, FW V4.7.6, A5E31298649B AG
Internal sequence control of the converter when the motor is switched on and off
Explanation
In this state, the converter does not respond to the ON command. The converter
goes into this state under the following conditions:
ON was active when switching on the converter.
Exception: When the automatic start function is active, ON must be active after
switching on the power supply.
OFF2 or OFF3 is selected.
This state is required to switch on the motor.
The converter waits for the operating enable.
The motor is switched on.
The motor was switched off with OFF1 and brakes with the ramp-down time of the
ramp-function generator.
The motor was switched off with OFF3 and brakes with the OFF3 ramp-down time,
or at the current limit.

Advanced commissioning

6.2 Inverter control
131

Advertisement

Table of Contents
loading

Table of Contents