Advanced commissioning

6.2 Inverter control
Bit
2
3
4
5
6
7
8, 9 Reserved
10
11
12
13
14
15
If you change over from another telegram to telegram 20, then the assignment of the previous
1)
telegram is kept.
142
Significance
Telegram 20
All other tele-
grams
0 = Quick stop (OFF3)
1 = No quick stop (OFF3)
0 = Inhibit operation
1 = Enable operation
0 = Disable RFG
1 = Do not disable RFG
0 = Stop RFG
1 = Enable RFG
0 = Inhibit setpoint
1 = Enable setpoint
0 → 1 = Acknowledge faults
0 = No control via PLC
1 = Control via PLC
1 = Direction reversal
Not used
---
1 = MOP up
1)
---
1 = MOP down Reduce the setpoint saved in the motorized
1)
CDS bit 0
Reserved
Explanation
Quick stop: The motor brakes with the OFF3
ramp-down time p1135 down to standstill.
The motor can be switched on (ON com-
mand).
Immediately switch-off motor (cancel pulses).
Switch-on motor (pulses can be enabled).
The inverter immediately sets its ramp-
function generator output to 0.
The ramp-function generator can be enabled.
The output of the ramp-function generator
stops at the actual value.
The output of the ramp-function generator
follows the setpoint.
The inverter brakes the motor with the ramp-
down time p1121 of the ramp-function genera-
tor.
Motor accelerates with the ramp-up time
p1120 to the setpoint.
Acknowledge fault. If the ON command is still
active, the inverter switches to"closing lockout"
state.
Inverter ignores the process data from the
fieldbus.
Control via fieldbus, inverter accepts the pro-
cess data from the fieldbus.
Invert setpoint in the inverter.
Increase the setpoint saved in the motorized
potentiometer.
potentiometer.
Changes over between settings for different
operation interfaces (command data sets).
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 06/2016, FW V4.7.6, A5E31298649B AG
Signal inter-
connection
in the in-
verter
p0848[0] =
r2090.2
p0852[0] =
r2090.3
p1140[0] =
r2090.4
p1141[0] =
r2090.5
p1142[0] =
r2090.6
p2103[0] =
r2090.7
p0854[0] =
r2090.10
p1113[0] =
r2090.11
p1035[0] =
r2090.13
p1036[0] =
r2090.14
p0810 =
r2090.15