Address Valid; Centralised Device Main-Sub - Panasonic CZ-256ESMC3 Technical Data Manual

Intelligent controller & communication adaptor
Hide thumbs Also See for CZ-256ESMC3:
Table of Contents

Advertisement

Various procedures
(05–02) Address valid
• Set whether the air conditioner is connected to air conditioner linked systems 1 or 2.

Address valid

0 (factory default)
1
2
3
[How to change]
1 Press and hold the SET key for at least 1 second and the address valid data blinks.
2 Press the UP or DOWN key to display the value you want to set.
(Select from 0 to 3 in the table above.)
3 Press and hold the SET key and when the display changes from blinking to lit, the change is
completed.
(05–03) Centralised device main-sub
• Set main and sub of the centralised control.
Address valid
0 (factory default)
1
2
3
[How to change]
1 Press and hold the SET key for at least 1 second and the main/sub setting data of centralised control
blinks.
2 Press the UP or DOWN key to display the value you want to set.
(Select from 0 to 3 in the table above.)
3 Press and hold the SET key and when the display changes from blinking to lit, the change is
completed.
Display and settings for the communication adaptor board
Air conditioner linked systems 1 Air conditioner linked systems 2
Air conditioner connected
Air conditioner connected
Air conditioner not connected
Air conditioner not connected
Air conditioner linked systems 1 Air conditioner linked systems 2
Main
Main
Sub
Sub
ー 28 ー
Air conditioner connected
Air conditioner not connected
Air conditioner connected
Air conditioner not connected
Main
Sub
Main
Sub