Various procedures
(04–06) Communication speed
• Displays the communication speed of the communication adaptor control wiring.
• The factory setting is 19,200 BPS.
• The following BPS can be selected.
1 19200 BPS ... Intelligent Controller (Do not change from this setting)
2 9600 BPS ... AMY software
[How to change]
1 Press and hold the SET key for at least 1 second and the BPS value blinks.
2 Press the UP or DOWN key to display 19200 and 9600 alternately.
3 Press and hold the SET key. When the display changes from blinking to lit, the change is completed.
4 It becomes valid after power supply restart of the communication adaptor board.
(04–07) Communication error detection interval
• Displays the time (minutes) until judging that a communication error with the air conditioner has occurred.
• The factory setting is 10 minutes.
• It can be set in the range from 0 to 99 minutes.
• If it is set to 0 minutes, communication error detection will not be performed.
Display and settings for the communication adaptor board
ー 23 ー