ID50 Series Panel - Installation, Commissioning & Configuration Manual
A
2
3
D
3
C
NOTIFIER
by Honeywell
ID50
ID60
NF30-A NF50-A
230VAC, 50Hz, 1.0A

2.5 Dismantling the Panel

For installation purposes, it is recommended that the
cover is removed from the back box and stored in a safe
place until ready for commissioning.
If any other trades, e.g. plasterers or decorators, will be
working in the vicinity after fitting the ID50 Series Panel,
it is strongly recommended that before re-fitting the cover
you remove the panel electronics and store in a safe place
until ready for commissioning. The main components
within the ID50 Series Panel are shown below.
B
C
D
E
ID50 Series Panel Assembly

2.5.1 Removing the Cover

To remove the ID50 Series Panel cover, it is
recommended that the following procedure is carried out
on a work bench BEFORE siting the panel on the wall:
1 Remove the four M3 x 6mm screws and washers (A)
2 Carefully withdraw the cover away from the back box,
3 Carefully detach the shrouded earth lead spade
Note: All blade connections to earth incorporate a locking
E
4 Remove and store the cover in a safe place.
The power supply ratings label (view 'E') is affixed to the
inside face of the fire control panel cover.
Before installing the back box, remove the panel
'E'
electronics (see Section 2.5.2, Panel Electronics).
A. Back box
B. PCB Assembly
C. LCD Unit
D. Fascia & Control Keypad
E. Cover
using a No. 1 Posidriv screwdriver, or the four hex
button-headed screws and clear washers (B) using a
2mm hex key, from the cover, and store safely.
until the earth blade terminal (C) within the cover is
accessible.
terminal (D) from the earth blade terminal (C) located
in the left-hand inner side wall of the cover.
barb. To make a connection push the shrouded
receptacle on to the earth blade (1). To remove
this connection, pull the shroud (2), NOT the earth
wire.
11
997-263-000-11, Issue 11
January 2010