ID50 Series Panel - Installation, Commissioning & Configuration Manual
* Loops can be configured to poll CLIP
devices or, when OPAL protocol is
enabled, a mixture of OPAL and CLIP
devices, providing no more than 10
CLIP devices are configured.
1 At maximum AC mains voltage (230V +10%)
2 At V
= 196 VAC and with panel fully loaded.
IN
997-263-000-11, Issue 11
January 2010
Controls:
Dedicated flush
pushbuttons are provided
for the following functions: MUTE BUZZER, EXTEND DELAY,
Additional pushbuttons for
configuration and selection
of software functions:
System Capacity:
Number of loops:
Number of zones:
Devices per loop:
External Connections:
Cable entry:
Terminals:
Electrical:
Classification:
Power Supply and Charger
Operating Voltage:
Voltage Tolerance:
Base card input:
Battery Charger output:
AUX DC Output Voltage:
EN54 Battery Wiring Test Impedance: 0.4 Ohm
EN54-4 PSU Loadings:
A1 - 2
END DELAY/EVACUATE, SILENCE/
RESOUND, RESET,
KEYS
2
4
6
8
KEY
5
KEY
0..9
KEY
10 BUTTON NUMERIC KEYPAD
1
32 (16 Fire + 16 Plant Alarm)
CLIP or OPAL* protocol: 99 sensors
+ 99 modules or 99 sensors +
combination of up to 99 modules/
sounders within strict limits.
16 x 20mm knock-outs in top of cabinet.
All external connections made
through screw terminals, each of
which will accept cable sizes
between 0.5mm
and 2.5mm
2
Installation Class 1, (panel must be
earthed).
230V 50Hz AC
+10% -15%
18V AC from integral mains
transformer.
27.1V nom. @ 20ºC (temperature
compensated and current limited).
Maximum output voltage = 29V
Minimum output voltage = 17.1V
I
= 350mA @26.0Vdc
max(a)
I
= 2.1A @26.0Vdc
max(b)
.
2
1
.
2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Notifier id60