Ve Outputs; Digital / Üe Inputs; Switch Connections - Honeywell Notifier ID50 Installation, Commissioning & Configuration Manual

Hide thumbs Also See for Notifier ID50:
Table of Contents

Advertisement

ID50 Series Panel - Installation, Commissioning & Configuration Manual
J2 - OUTPUT D
1
2
3
4
5
6
7
8
J1 - OUTPUT C
2
1
3
4
5
6
7
8
Unmonitored Relays
The unmonitored relay Output C is factory set as a fault
output, and Output D as a fire output. When configured
as volt-free relay outputs, the outputs are NOT power-
limited.
If these connections are to be configured as unmonitored
relays make sure that:
a. Jumper Links are set accordingly, refer to
Section 4.3.1, Jumper Link Options,
b. Correct polarity is used when terminating at the back
box, i.e. terminal 1 being normally-open (or normally-
closed) and terminal 2 being common contact.
Maintain adequate segregation from power-limited
wiring.

4.4.6 -VE Outputs

The two -VE Outputs, located at TB2 at the bottom left-
hand corner of the PCB assembly, are normally used to
provide a DC power supply for up to two relays located
externally to the panel.
When the -VE Outputs are initially connected, the default
software outputs are set as follows:
a. Output 1 - Pre-Alarm and
b. Output 2 - Plant Warning.
During commissioning these outputs can be individually
configured to become active if any fire alarm, pre-alarm,
fault or plant warning conditions occur (see Section 5,
Configuration).
4.4.7 Digital / ÜE Inputs (TB8)
These inputs are located at the bottom centre of the PCB
assembly. Digital Input 1 can be configured for use as
either a Day Mode or Class Change function. To select
the required function use the 'Digital Input 1' menu, see
Section 5.5.3.8 Digital Input 1.
Digital Input 2 is currently not supported.

4.4.8 Switch Connections

KEY-SW
The Key Switch connector is a digital input on the PCB.
Operation of the key switch permits access at level 2.
Cover Switch
This connector is not used.
31
997-263-000-11, Issue 11
January 2010