ID50 Series Panel - Installation, Commissioning & Configuration Manual
EN54-2 : 7.6.1, 7.8, 8.7.1,
9.1.2
Ensure EN54 compliance
for access to controls.
1
or
2
DISABLEMENT
TEST
POWER SUPPLY FAULT
DELAYS ACTIVE
FIRE OUTPUT: FAULT / DISABLED
FIRE OUTPUT ACTIVE
SOUNDER: FAULT / DISABLED
POWER
FIRE CONTROL O/P: FAULT / DISABLED
PLANT ALARM
FAULT O/P: FAULT / DISABLED
1
or
2
5.5.1.3 Control Keys Access Level
EN54-2 requires the following access to controls:
Level 2: Reset (EN54-2 Clauses 7.6.1 & 8.7.1)
Level 1: End Delays (or MCP) (EN54-2 Clause 7.11d).
The Control Keys option allows the access level at which
the panel control keys can be operated to be changed.
To select the required access level:
1 From the Setup menu screen, using the numeric
[Setup] Language =
> : Change
8
2 Press the '
[Setup]
> : Change
3 Press the '
4 Press '
5.5.1.4 LED 1H Mode
FAULT
The default function for this LED is PLANT ALARM. This option
allows this LED on panels with the new 5-button membrane
EARTH FAULT
to be configured as FAULT O/P: FAULT/DISABLED.
SYSTEM FAULT
[S1
Setup]
PRE- ALARM
2: Site Details
[S1
1 From the Setup menu, using the numeric keypad press
[Setup] Language =
> : Change
8
2 Press the '
[Setup]
> : Change
41
Silence Sounders (EN54-2 Clause 7.8)
Extend Delays (EN54-2 Clause 9.1.2)
keypad press the '
' button to enter the Panel
1
Options menu. The Language screen is displayed first.
English
/
' buttons to step through the Panel
2
8
Options menus until the Control Keys screen is
displayed.
Control Keys Access Level = 2
' button to change the setting to level 1
6
(no passcode) or level 2 (user passcode). The default
access level is level 2.
' to return to the Setup menu screen. All
4
changes will be saved on exiting.
1: Panel Options
3: Device Options
Setup]
4: Peripheral Options
5: Day / Night Settings
the '
' button to enter the Panel Options menu. The
1
Language screen is displayed first.
English
/
' buttons to step through the Panel
2
8
Options menus until the LED 1H Mode screen is
displayed.
LED 1H =
: More
< : Exit
: More
< : Exit
: More
: More
: More
< : Exit
Plant Alarm
: More
< : Exit
997-263-000-11, Issue 11
January 2010