Conversion To High Elevation; Gas Pipe Pressure Testing - Regency Ultimate U39E Series Owners & Installation Manual

Freestanding gas stove
Hide thumbs Also See for Ultimate U39E Series:
Table of Contents

Advertisement

installation

Conversion to High Elevation

THIS CONVERSION MUST BE DONE BY A QUALIFIED GAS
FITTER IF IN DOUBT DO NOT DO THIS CONVERSION !!
Natural Gas Conversion Kit 730-920 Contains:
Qty. Part # Description
1 904-240 Burner Orifice #37 (NG)
1 918-034 Decal "Converted to 31,000 Btu"
1 918-033 Instruction Sheet
Propane Conversion Kit 730-922 Contains:
Qty. Part # Description
1 904-390 Burner Orifice #52 (LPG)
1 918-034 Decal "Converted to 29,000 Btu"
1 918-033 Instruction Sheet
1) Shut off the gas supply.
2) Open the front door. Carefully remove the logs
and media.
3) Remove burner. See diagram below.
4) Remove burner orifice with a 1/2" wrench and
discard.
Note: Use a magnetic type screwdriver if
possible.
|
32
Regency
U39E-11 ULTIMATE™ Freestanding Gas Stove
®
Burner Orifice
5) Reinstall new burner orifice (NG stamped #37)
and tighten.
6) Reverse steps 3) and 2).
7) Attach the label "This unit has been converted
to..." on top of the serial # decal over the higher
Btu information.
8) Check for gas leaks.
9) Check inlet and outlet pressures.
10) Check operation of flame control. Check for
proper flame appearance and glow on logs.

Gas Pipe Pressure Testing

The appliance must be isolated from the gas supply
piping system by closing its individual manual shut-
off valve during any pressure testing of the gas
supply piping system at test pressures equal to or
less than 1/2 psig. (3.45 kPa). Disconnect piping
from valve at pressures over 1/2 psig.
The manifold pressure is controlled by a regulator
built into the gas control, and should be checked
at the pressure test point.
Note: To properly check gas pressure,
both inlet and manifold pressures
should be checked using the valve
pressure ports on the valve.
1. Make sure the valve is in the "OFF" position.
2. Loosen the "IN" and/or "OUT" pressure tap(s),
turning counter clockwise with a 1/8" wide flat
screwdriver.
3. Attach manometer to "IN" and/or "OUT" pressure
tap(s) using a 5/16" ID hose.
4. Light the pilot and turn the valve to "ON" position.
Read manometer.
5. The pressure check should be carried out with
the unit burning and the setting should be within
the limits specified on the safety label.
6. When finished reading manometer, turn off the
gas valve, disconnect the hose and tighten the
screw (clockwise) with a 1/8" flat screwdriver.
Note: Screw should be snug, but do not over
tighten