Position of the IM 151-7 CPU in the CPU Range
Porting with packed addresses
If FBs with packed I/O addresses are copied to the IM 151-7 CPU, the packed
addresses there can no longer be assigned to the I/Os of the I/O modules locally
because the CPU of the IM 151-7 CPU cannot work with packed addresses. This
requires rewiring of the corresponding FBs. Rewiring corresponds to "unpacking"
the addresses.
Figure 12-2
Rewiring
The following blocks and address IDs can be rewired:
S Inputs, outputs
S Memory markers, timers, counters
S Functions, function blocks
Proceed as follows to rewire the signals:
1. In SIMATIC Manager, select the "Blocks" folder, which contains the blocks with
the packed addresses that you want to port to the IM 151-7 CPU.
2. Select the menu command Tools ! Rewire.
3. Enter the desired replacements in the displayed "Rewiring" dialog box in the
table (old address ID/new address ID).
Table 12-2 Example : Replacements under Tools ! Rewire
1
I 1.2
2
I 1.3
12-4
I1.0
DI_1_module
I1.1
I1.2
DI_2_module
I1.3
Example: FB with packed addresses
Old address ID
O1.0
O1.1
New address ID
I 2.0
I 2.1
ET 200S IM 151-7 CPU Interface Module
A5E00058783-04