Commissioning and Diagnostics
7.1

Configuring the IM 151-7 CPU

Configure the interface module IM 151-7 CPU as the following:
S I slave
S I slave and DP master
S Stand-alone module (MPI)
S Stand-alone module (MPI) and DP master
The IM 151-7 CPU is presented to the user in STEP 7 as an S7-300 module that is
always created together with a rack in an S7-300 station. Similarly, the module can
only be deleted with the rack!
Expansion racks cannot be configured in an S7-300 station that contains an
IM 151-7 CPU. The IM 151-7 CPU is positioned at slot 2 and receives an MPI/DP
submodule. The first plug-in modules can be configured as of slot 4.
The following configuration options are available:
Table 7-1
Configuration
environment
SIMATIC S7
SIMATIC S5
Non-Siemens
systems
Note
If you wish to operate the IM 151-7 CPU as a standard I slave via the GSD file,
then you should not activate the commissioning/test mode checkbox in the DP
interface properties when configuring this slave CPU in STEP 7.
Information on configuring the DP master functionality is provided in Chapter 6.2.
7-2

Configuration options

Configuration tool
STEP 7 (HWConfig)
V5.1 or higher + SP4
STEP 7 (HWConfig)
V5.2 or higher + SP1
COM PROFIBUS
Non-Siemens tool
Configurable operating mode
S
Stand-alone (MPI)
S
IM 151-7 CPU as S7 slave
IM 151-7 CPU with the DP
master module as the DP master
Fully configured and programmed
IM 151-7 CPU, integrated as a
standard intelligent slave via GSD
in COM PROFIBUS
Fully configured and programmed
IM 151-7 CPU, integrated as a
standard intelligent slave via GSD
in a non-Siemens tool
ET 200S IM 151-7 CPU Interface Module
A5E00058783-04