Applicable Standards - Omron 3G3RX2-A2 Series Instruction Manual

Table of Contents

Advertisement

Inverter Specifications
Common specifications (continued)
Output terminal function
Output
Relay and alarm relay
(1a, 1c)
EDM output terminal
Monitor output terminal *8
EMC filter switching *9
External access to PC
Ambient temperature *14
Storage temperature *10
Use
environment
Humidity
Vibration *11
Use location *12
Expected Life time

Applicable standards *13

Painting color
Operation and monitor
Number of option slots
Other options
*7. The threshold for signal output varies depending on the motor to be combined with the inverter, parameter adjustment, etc.
*8. The output data of analog voltage monitor and analog current monitor are reference values for connecting an analog meter. Due to the meter to be con-
nected and variation in analog output circuit, the maximum output value may slightly vary from 10V or 20mA. To change characteristics, make adjustments
using the Ao1 adjustment and Ao2 adjustment functions. Some monitor data cannot be output.
*9. To enable the EMC filter, connect with a power supply grounded at a neutral point. Otherwise, the leakage current may increase.
*10. The storage temperature is the temperature during transport.
*11. To be in accordance with the testing method specified in JIS C 60068-2-6: 2010 (IEC 60068-2-6:2007)
*12. When the inverter is used in a location at 1000m or higher altitude, air pressure reduces approximately 1% every 100m elevation. Perform 1% current der-
ating and conduct evaluation for every 100m elevation. Please contact us for use in 2500m or higher environments.
*13. For insulation distance, comply with UL and CE standards
*14. Use the 400V class inverter at an input voltage of 500VAC or below. If input voltage exceeds 500VAC due to fluctuation of power, use the inverter at 40°C
or lower ambient temperature.
*15. In the case where a clock function is used, a battery (Option:CR2032, 3V) is required. When you purchase the product, the LCD operator does not have its
battery.
 Applicable Standards
Markings
EMC
CE
Machinery
US
CA
UL
FS
KC
EAC
RCM
14
Transistor output 5 terminal, 1a contact relay 1 point, 1c contact relay 1 point
RUN (During operation), FA1-5 (Reached signal), IRDY (Operation ready completion), FWR (During normal
rotation operation), RVR (During reverse rotation operation), FREF (Frequency command operator keypad),
REF (Operation command operator keypad), SETM (Second control under selection), AL (Alarm signal), MJA
(Severe failure signal), OTQ (Over torque) *7, IP (During instantaneous power failure), UV (Under insufficient
voltage), TRQ (During torque limitation), IPS (During power failure deceleration), RNT (RUN time over), ONT
(Power on time over), THM (Electronic thermal warning), THC (Electronic thermal warning), WAC (Capacitor life
advance notice), WAF (Fan life advance notice), FR (Operation command signal), OHF (Cooling fin heating
advance notice), LOC/LOC2 (Low-current signal), OL/OL2 (Overload advance notice), BRK (Brake release),
BER (Brake abnormality), ZS (Zero-speed detection signal), OD/OD2 (PID deviation excessive), FBV/FBV2 (PID
feedback comparison), NDc (Communication disconnection), Ai1Dc/Ai2Dc/Ai3Dc (Analog disconnection
Ai1/Ai2/Ai3), WCAi1/WCAi2/WCAi3 (Window comparator Ai1/Ai2/Ai3), LOG1-7 (Logical operation result 1-7),
MO1-7 (General output 1-7), and OVS (Receiving overvoltage).
Output for STO diagnosis
Possible to output through selection from monitor data of parameters
Possible to enable the EMC noise filter (switching method is different depending on the model)
USB Micro-B
ND (normal duty)
-10 to 50°C
LD (low duty)
-10 to 45°C
VLD (very low duty)
-10 to 40°C
-20 to 65°C
20-90%RH (location free of condensation)
2
5.9m/s
(0.6G) 10 to 55Hz : 3G3RX2-A2004 to A2220 / 3G3RX2-A4007 to A4220
2
2.94m/s
(0.3G) 10 to 55Hz : 3G3RX2-A2300 to A2550 / 3G3RX2-A4300 to A413K
1000 m altitude or lower (location free from corrosive gas, oil mist, and dust)
Smoothing capacitor 10 years
Designed life of cooling fan 10 years (models equipped with a cooling fan) free from dust
Memory element on the control circuit board
Compliance with UL/cUL/CE standards, RCM, Functional Safety SIL3/PLe (to be obtained)
Black
LCD operator *15
3 ports
Braking resistor, AC reactor, DC reactor, noise filter
Standards
EN 61800-3:2004+A1:2012
IEC61800-5-2:2016 STO SIL3
ISO13849-1:2015 Cat.4 PLe
IEC61800-5-1/A1:2016
UL61800-5-1
CSA C22.2 No. 274
IEC61800-5-2:2016 STO SIL3
ISO13849-1:2015 Cat.4 PLe
KN61800-3
-
EN 61800-3:2004+A1:2012

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents