Control circuit
■RS485 Communication Terminal
CM1
SP
(+)
Connect CM1 to the SG
(signal ground) of an
external device.
SP and SN terminals with the same names are internally connected respectively, so they can be used
for wiring multiple terminals.
Serial
RS485 com-
communi-
munication
cation
34
Modbus communication
SN
SP
SN
RP
(-)
When enabling the terminating
resistor, short RP-SN.
Terminal
Terminal
symbol
name
RS-485
SP
terminal
SN
for Modbus
RP
communi-
(CM1)
cation
Control circuit terminal area
Description
SP terminal: RS-485 differential (+) signal
SN terminal: RS-485 differential (-) signal
RP terminal: Connect to SP via tile terminating
resistor
CM1 terminal: Connect with the signal ground
of an external communication device.
(also used by FM terminal)
There are two SP terminals and SN terminals
each, which are connected internally.
Maximum baud rate is 115.2kbps.
Electrical character-
istics
Equipped with termi-
nating resistor
(120Ω)
Enable: Short RP-SN
Disable: Open RP-SN