■Output terminals
(Wiring example)
Open
collector
Output
Digital
terminal
output
Relay
Terminal
Terminal
symbol
name
15, 14
Output
You can select terminal functions
terminal
using the parameter settings corre-
13, 12
sponding to each terminal.
11
These terminals can be used both in
sink logic or source logic.
CM2
Common
Common terminals for output termi-
for output
nals 11-15
terminal
16A
1a relay
A relay for contact A output.
terminal
16C
AL0
1c relay
A relay for contact C output.
terminal
AL1
AL2
Description
Electrical characteristics
Open collector output
• Between each terminal and CM2
• Voltage drop at ON: 4V or below
• Maximum allowable voltage: 27V
• Maximum allowable current:
50mA
Maximum capacity of contact
• AC250V, 2A (resistance)
• AC250V, 1A (induction)
Minimum capacity of contact
• DC1V, 1mA
Maximum capacity of contact
AL1/AL0:
• AC250V, 2A (resistance)
• AC250V, 0.2A (induction)
AL2/AL0:
• AC250V, 1A (resistance)
• AC250V, 0.2A (induction)
Minimum capacity of contact (com-
mon)
• AC100V, 10mA
• DC5V, 100mA
Control circuit