Main circuit
■Applicable Breakers
 200V class
• When inverter ND rating setting
Model
3G3RX2
A2004
A2007
A2015
A2022
A2037
A2055
A2075
A2110
A2150
A2185
A2220
A2300
A2370
A2450
A2550
• When inverter LD/VLD rating setting
Model
3G3RX2
A2004
A2007
A2015
A2022
A2037
A2055
A2075
A2110
A2150
A2185
A2220
A2300
A2370
A2450
A2550
Note
1.
The models described in the table are examples of selection. When using the device, choose a model that has appropriate
breaking capacity and sensitive current by taking short circuit current and relevant laws and regulations into consideration
based on the rated current shown in the table.
2.
The applicable motor capacity is a selection example when standard motors 4-pole motor model 60HZ 200VAC (200V class)
is used.
3.
The electric durability ensured when the magnetic contactor is used in AC-1 class is 500,000 times, while emergency stop
during motor operation is 25 times.
4.
If there is emergency stop during motor drive or commercial operation is performed, choose the magnetic contactor on the
motor side in AC-3 class against the rated current of motor.
5.
If the rated capacity of inverter is larger than the motor capacity, choose instruments based on the inverter model.
24
Without power factor improvement reactor
Applicable
motor
Earth-leakage breaker
(kW)
(ELB)
Example
Rated
of model
current
0.4
EB-30E
5
0.75
EB-30E
10
1.5
EB-30E
15
2.2
EB-30E
20
3.7
EB-30E
30
5.5
EB-50E
40
7.5
EB-50E
50
11
EB-100E
75
15
RXK125-S
125
18.5
RXK125-S
125
22
EXK225
150
30
EXK225
200
37
RXK250-S
250
45
EX400
300
55
EX400
400
Without power factor improvement reactor
Applicable
motor
Earth-leakage breaker
(kW)
(ELB)
Example
Rated
of model
current
0.75
EB-30E
10
1.5
EB-30E
15
2.2
EB-30E
20
3.7
EB-30E
30
5.5
EB-50E
40
7.5
EB-50E
50
11
EB-100E
75
15
RXK125-S
125
18.5
RXK125-S
125
22
EXK225
150
30
EXK225
200
37
RXK250-S
250
45
EX400
300
55
EX400
400
75
EX600B
500
Applicable instrument (input voltage 200 to 220V)
With power factor improvement reactor
Magnetic contactor
Earth-leakage breaker
(MC)
Example
AC-1
AC-3
of model
HS8
HS8
EB-30E
HS8
HS8
EB-30E
HS8
HS8
EB-30E
HS8
HS8
EB-30E
HS8
HS20
EB-30E
HS20
HS25
EB-30E
HS35
HS35
EB-50E
HS50
H65C
EB-100E
H65C
H80C
EB-100E
H80C
H100C
EB-100E
H80C
H125C
RXK125-S
H125C
H150C
EXK225
H150C
H200C
EXK225
H200C
H250C
EXK225
H200C
H300C
EX400
Applicable instrument (input voltage 200 to 220V)
With power factor improvement reactor
Magnetic contactor
Earth-leakage breaker
(MC)
Example
AC-1
AC-3
of model
HS8
HS8
EB-30E
HS8
HS8
EB-30E
HS8
HS8
EB-30E
HS8
HS20
EB-30E
HS20
HS25
EB-30E
HS35
HS35
EB-50E
HS50
H65C
EB-100E
H65C
H80C
EB-100E
H80C
H100C
EB-100E
H80C
H125C
RXK125-S
H125C
H150C
EXK225
H150C
H200C
EXK225
H200C
H250C
EXK225
H200C
H300C
EX400
H300C
H400C
EX400
(3G3AX-AL or 3G3AX-DL)
Magnetic contactor
(ELB)
(MC)
Rated
AC-1
AC-3
current
5
HS8
HS8
5
HS8
HS8
10
HS8
HS8
15
HS8
HS8
20
HS8
HS20
30
HS8
HS20
40
HS20
HS25
60
HS35
HS50
100
HS50
H65C
100
HS50
H65C
125
H65C
H80C
150
H80C
H125C
200
H100C
H125C
225
H125C
H150C
300
H150C
H250C
(3G3AX-AL or 3G3AX-DL)
Magnetic contactor
(ELB)
(MC)
Rated
AC-1
AC-3
current
5
HS8
HS8
10
HS8
HS8
15
HS8
HS8
20
HS8
HS20
30
HS8
HS20
40
HS20
HS25
60
HS35
HS50
100
HS50
H65C
100
HS50
H65C
125
H65C
H80C
150
H80C
H125C
200
H100C
H125C
225
H125C
H150C
300
H150C
H250C
400
H200C
H300C

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents