Conditions of conformity of EU directives
b) According to EN61800-3 it is mandatory to mention that any inverter with only C3 filter inside
may NOT be connected to a low voltage public power supply in residential areas since for these
installations C1 is required.
c) In case of external filter for C2, an additional note is required according to EN61800-3 that "this
product may emit high frequency interference in residential areas which may require additional
EMC measures".
d) According to the EN6100-3-12, an additional AC reactor or DC choke should be installed for
reducing harmonics in power line.
3. Wiring requirements
a) A shielded wire (screened cable) must be used for motor wiring, and the length of the cable must
be according to the following table.
b) The carrier frequency must be set according to the following table to meet an EMC requirement.
c) The main circuit wiring must be separated from the control circuit wiring.
4. Environmental requirements (to be met when a filter is used)
a) 3G3RX2 series inverter that is activated built-in EMC filter must be according to 3G3RX2 series
specifications.
Table 1
Model
3G3RX2
A2004
A2007
A2015
A2022
A2037
A2055
A2075
A2110
A2150
A2185
A2220
A2300
A2370
A2450
A2550
---
---
---
---
■Conditions of Electrical Safety (LVD)
The condition in the next section UL standard explain the condition of the electrical safety. It is neces-
sary to comply with the description items such as temperature condition, installation condition etc.
38
Carrier
Cat.
Cable length
frequency
C3
10m
2kHz
C3
10m
2kHz
C3
10m
2kHz
C3
10m
2kHz
C3
10m
2kHz
C3
5m
2kHz
C3
5m
2kHz
C3
5m
2kHz
C3
10m
1kHz
C3
10m
1kHz
C3
10m
1kHz
C3
5m
2kHz
C3
5m
2kHz
C3
5m
2kHz
C3
5m
2kHz
---
---
---
---
---
---
---
---
---
---
---
---
Model
Cat.
Cable length
3G3RX2
--
--
--
A4007
C3
10m
A4015
C3
10m
A4022
C3
10m
A4037
C3
10m
A4055
C3
5m
A4075
C3
5m
A4110
C3
5m
A4150
C3
10m
A4185
C3
10m
A4220
C3
10m
A4300
C3
5m
A4370
C3
5m
A4450
C3
5m
A4550
C3
5m
B4750
C3
3m
B4900
C3
3m
B411K
C3
3m
B413K
C3
3m
Carrier
frequency
--
2kHz
2kHz
2kHz
2kHz
2kHz
2kHz
2kHz
2kHz
2kHz
2kHz
2kHz
2kHz
2kHz
2kHz
2kHz
2kHz