X13 Ser_Opt2, Rs232 Connection Terminal; Technical Data - Siemens 13-xx-ST-SBT Series Product Data

Fire detection system
Table of Contents

Advertisement

32.3.5
32.4
Plug-in units
Supply
Connections
Mechanical data
Ambient conditions
Standards and approvals
Building Technologies
Fire Safety

X13 SER_OPT2, RS232 connection terminal

Pin
Designation
6
CTS
5
GND
4
RXD
3
2
TXD
1
RTS
Admissible cable cross-section: 0.2...1.5 mm²
SER_OPT2
X13
CTS
GND
RXD
TXD
RTS
T Participant with RS232 interface

Technical data

Slots
Operating voltage
Operating current
Permitted cable cross section (plug X10)
screw terminals
Total current of all module bus cards
I/O
Permitted cable cross section (plug
X41...X52) screw terminals
Interfaces
Dimensions (L x W x H)
Weight
Shielding
Operating temperature
Storage temperature
Air humidity
VDS
QA Standards
CE conformity mark
LPCP
Processor unit (19", FC2080) FCC2002-A1
Description
Clear To Send
Ground
Received Data
Transmitted Data
Ready To Send
6
5
4
T
3
2
1
Max. 5 cards
2 CPU cards
1 communication card
2 module bus cards I/O
Vsys
Max. 8 A
0.5...2.5 mm²
Max. 6.9 A
Max. 2 A
0.14...1.5 mm²
2 x module bus cards, 1 x RS232, 1 x
RS485, 2 x SAFEDLINK
296 x 190 x 140 mm
960 g
Housing with cover: Steel sheet
Min. -5 °C max. +40 °C
Min. -20
Max. 93 % rel. air humidity (EN 60068-2)
Technical data
max. +60
008837_q_en_--
14.05.2012
32
191