19.4
LED
Color
Function
V DC
Green
Supply
FAIL
Red
Error
RX
Yellow
Data line
STA
Red
Status
19.5
Building Technologies
Fire Safety

Indicators

Condition
Meaning
Off
No operating voltage available
On
+24 V voltage available on VDC1 or VDC2
Off
Normal condition
On
Data error
Off
No data transfer
On
Data is being received
Off
Normal condition
On
Optical receiving signal incorrect

Adjustment elements

The terminating resistor needed for the bus is selected using the DIP switch.
R
= wave resistance
W
R
= pull-up resistance
PU
R
= pull-down resistance
PD
Switch
Designation
6
5
4
3
R
W
2
R
PU
1
R
PD
6
1
Interface module DL485/13-xx-ST-SBT
Position
Function
OFF
Not connected
OFF
Not connected
OFF
Not connected
ON
120
between the data lines
ON
390
following +5 V
ON
390
following 0 V