Adjustment Elements; Set Button - Siemens 13-xx-ST-SBT Series Product Data

Fire detection system
Table of Contents

Advertisement

20
Ethernet switch (MM) FN2008-A1

Adjustment elements

20.5
20.5.1
Phase
Time for which
button is pressed
1
<3 s
2
3...6 s
3
6...8 s
4
8...10 s
5
10...15 s
6
> 15 s
126
Building Technologies
Fire Safety
Indicators for device powering up
When the device is powering up, the following LEDs light up in the sequence
shown:
1. Power LEDs (L) light up as soon as voltage is present.
2. Port LEDs (P1...P6) light up yellow for around 6 s.
3. Port LEDs go out. Once the port LEDs have gone out, the correct link status is
displayed after around 2 s.
4. The red fault LED lights up for around 20 s.
The FN2008-A1 is then ready.
Adjustment elements

Set button

Set button
The 'Set' button can be used to change various FN2008-A1 settings. Changed
settings are retained even after switching off.
Different settings are undertaken depending on how long the button is pressed for.
Six setting phases are possible:
3
1
2
0 s
3 s
6 s
Set button phases
Function
The detector screen currently set is displayed. If no detector screen has been set, all port
LEDs flash in turn.
If the button is released during phase 1, this will have no effect.
The LEDs of the linked ports flash at 2.5 Hz.
If the button is released during phase 2, this will have no effect.
The LEDs of the linked ports and the LEDs of the connected voltage supply light up.
If the button is released during phase 3, the detector screen is adopted according to the
LEDs lit up.
The RM LED flashes.
If the button is released during phase 4, the redundancy manager is shut down. The
redundancy function is however retained.
The device switches into 'Automatic redundancy detect' operating mode.
The RM LED lights up.
If the button is released during phase 5, the redundancy function is activated and the
device configured as HSR manager.
All LEDs flash.
The device is reset to the factory setting.
4
5
6
8 s
10 s
15 s
008837_q_en_--
14.05.2012