Fiber optic network module FN2006 / FN2007
Technical data
Fibre optic cable
FCnet
Mechanical data
Ambient conditions
Standards
110
Building Technologies
Fire Safety
Type of connection
Wavelength
Multi-mode
Range:
Fiber type 62.5/125 µm
Fiber type 50/125 µm
Optical budget:
Fiber type 62.5/125 µm
Fiber type 50/125 µm
Single mode
Range:
Fiber type 9/125 µm
Optical budget:
Fiber type 9/125 µm
Minimum optical attenuation
(corresponds to a minimum fiber
length of 4000 m)
Length of line
Impedance
Transmission mode
Cable type
Plug connection
Dimensions (H x W x D)
Weight
Operating temperature
Storage temperature
Rel. humidity during operation
SC connector
1310 nm
4 000 m
2000 m
11 dBm
7.5 dBm
40,000 m
29 dBm
3 dBm
Max. 1,000 m, total length of the electric connection
between two network modules (FN2001 or FN2010)
120
Half-duplex
Shielded and unshielded cables
Example:
Uninet 30044PFRNC(KAT6)
R&M freenet KAT5e F/UTP 4P
Communication cable J-2T(St)TSTIIIBD
CCM 2C1.5T1/1254(MICC)
Fire detection cable JY(St)Y2 x 2 x 0.8 mm red
Phoenix PSC (connector included in accessories)
140 x 110 x 35 mm
570 gr.
-10...+55 °C
-30...+75 °C
95 %, non-condensing