Siemens 13-xx-ST-SBT Series Product Data page 185

Fire detection system
Table of Contents

Advertisement

Monitored sound input
Monitored sound output 1, 2,
3, 4
Connection terminals
Mechanical data
Building Technologies
Fire Safety
Designation
Individual sounder module:
Resistance value standby
Tolerance
Two sounder modules parallel:
Resistance value standby
Tolerance
Designation
Design
Output voltage
Output current
Guaranteed output current (monitored for
short-circuit and open line)
Monitored for (if output inactive)
Monitoring resistance
With tolerance
Max. connection distance
All connectors:
Design
Admissible cable cross-section
Dimensions (L x W x H)
Weight
The monitoring resistance must also be connected when the sound output is not
1
used.
The operating current is max. 2 A (fuse protection 2AT) although the max. output
2
current per sounder is 1 A.
I
2 A = I
+ I
+ I
total max.
Out1
Out2
If the sounder module FCA2005 is fed via the peripheral board (output VSYS), the
availability of a maximum current of 1 A (1 A fuse) on this output must be observed.
The maximum operating current I
NOTICE! Some voltage ranges of certified horns are limited to 28 V. This
maximum voltage can only be guaranteed if the control panel temperature is
always >5 °C.
Sounder module FCA2005-A1
'Sound In+', 'Sound In-'
4900
+/-300
2450
+/-300
'S1 out+', 'S1 out-'
'S2 out+', 'S2 out-'
'S3 out+', 'S3 out-'
'S4 out+', 'S4 out-'
Relay reversed polarity
DC 21...28.6 V
Max. 1 A / sounder
(observe maximum current)
15 mA when U
Short-circuit
Open line
3 k
1
+/-500
1000 m
Screw terminals
0.8 ... 1.5 mm
132 x 90 x 24 mm
120 g
+ I
Out3
Out4
is only 1 A in this case.
total max
31
Technical data
2
= 16 V
outmin
2
185
008837_q_en_--