Pin Assignments; X12 Detector Line Loop 2 - Siemens 13-xx-ST-SBT Series Product Data

Fire detection system
Table of Contents

Advertisement

Element
LEDs
Fuses
Adjustment elements

7.3 Pin assignments

7.3.1
Building Technologies
Fire Safety
Des.
Function
H1
Power Down Ready
H201
Display FDnet module 2
H401
Monitoring supply output 1 (fuse F401)
H402
Monitoring supply output 2 (fuse F402)
H501
Monitoring alarm output (fuse F501)
H601
Monitoring fault output (fuse F601)
Indications of programmable inputs and outputs
H100-
H115
F400
Horn output (1 A/T); Schurter OMT 125
F401
Supply output 1 (1 A/T); Schurter OMT 125
F402
Supply output 2 (1 A/T); Schurter OMT 125
F501
Monitored alarm output (1 A/T); Schurter OMT 125
F601
Monitored fault output (1 A/T); Schurter OMT 125
S100
Switchover of the LED indicators for the inputs and outputs
Inputs and outputs which are not used do not require termination.
FDnet detector lines which are not used must not be terminated.

X12 detector line loop 2

Pin
Designation
4
LOOP2_2–
3
LOOP2_2+
2
LOOP2_1–
1
LOOP2_1+
Admissible cable cross-section: 0.2...1.5 mm²
LOOP2_2-
LOOP2_2+
LOOP2_1-
LOOP2_1+
One loop or two stubs can be connected.
Periphery board (2 loops) FCI2002-A1
Description
Loop 2 / stub 4 (–)
Loop 2 / stub 4 (+)
Loop 2 / stub 3 (–)
Loop 2 / stub 3 (+)
X12
-
4
3
+
-
2
+
1
7
Pin assignments
53
008837_q_en_--
14.05.2012