Siemens 13-xx-ST-SBT Series Product Data page 62

Fire detection system
Table of Contents

Advertisement

7
Periphery board (2 loops) FCI2002-A1
Technical data
Configurable inputs/outputs
1...8
Connection terminals
Mechanical data
62
Building Technologies
Fire Safety
Designation
Individually configurable as
Configured as input:
Design
Threshold values
Configured as output:
Design
Output voltage
Output current per output
Output current of all outputs (total)
Inputs, outputs and detector line
Design
Admissible cable cross-section
Supply:
Design
Admissible cable cross-section
Dimensions (L x W x H)
Weight
Some voltage ranges of certified horns are limited to 28 V. This maximum voltage
1
can only be guaranteed if the control panel temperature is >5 °C.
'I/O1' ... 'I/O8'
Input
Output
Digital
Not monitored
> Vsys/2 = off
< Vsys/4 = on
Open drain
Inherently short-circuit-proof
Excess temperature protection
DC 21...28.6 V
Max. 300 mA
1 A
Spring clips
0.2...1.5 mm²
Screw terminals
0.5...2.5 mm²
210 x 150 x 40 mm
220 g
008837_q_en_--
14.05.2012

Advertisement