Controls At Mode Changing / Start-Up - Daikin FTXS09DVJU Service Manual

Inverter pair wall mounted type
Hide thumbs Also See for FTXS09DVJU:
Table of Contents

Advertisement

Control Specification (15/18/24 Class)
4.3

Controls at Mode Changing / Start-up

4.3.1
Preheating Operation
Outline
Operate the inverter in the open phase operation with the conditions including the preheating
command from the indoor, the outdoor air temperature and discharge pipe temperature.
Detail
Preheating ON Condition
OFF Condition
4.3.2
Four Way Valve Switching
Outline
Heat Pump Only
During the heating operation current must be conducted and during cooling and defrosting current
must not be conducted. In order to eliminate the switching sound (as the four way valve coil
switches from ON to OFF) when the heating is stopped, the delay switch of the four way valve must
be carried out after the operation stopped.
Detail
The OFF delay of four way valve
Energize the coil for 150 sec after unit operation is stopped.
4.3.3
Four Way Valve Operation Compensation
Outline
Heat Pump Only
At the beginning of the operation as the four way valve is switched, acquire the differential pressure
required for activating the four way valve by having output the operating frequency, which is more
than a certain fixed frequency, for a certain fixed time.
Detail
Starting Conditions
1. When starting compressor for heating.
2. When the operating mode changes from the previous time.
3. When starting compressor for starting defrosting or resetting.
4. When starting compressor for the first time after the reset with the power is ON.
4.3.4
3 Minutes Stand-by
Prohibit to turn ON the compressor for 3 minutes after turning it off.
(except when defrosting)
50
When outdoor air temperature and discharge pipe temperature are below 51ºF, inverter in open
phase operation starts.
When outdoor air temperature or discharge pipe temperature is higher than 54ºF, inverter in
open phase operation stops.
Set the lower limit frequency to 55 (model by model) Hz for 70 seconds with any conditions 1
through 4 above.
SiUS04-702
Function and Control