Control Specification
3.3

Controls at Mode Changing / Start-up

3.3.1 Preheating Control
Outline
The inverter operation in open phase starts with the conditions of the preheating command from
the indoor unit, the outdoor temperature, and the discharge pipe temperature.
Outdoor temperature ≥ A°C → Control I
Detail
Outdoor temperature < A°C → Control II
Control I
Control II
3.3.2 Four Way Valve Switching
Outline
In heating operation, current is conducted, and in cooling operation and defrost control, current
is not conducted. In order to eliminate the switching sound as the four way valve coil switches
from ON to OFF when the heating is stopped, the OFF delay switch of the four way valve is
carried out.
Detail
OFF delay switch of four way valve
The four way valve coil is energized for 150 ~ 160 seconds after the operation is stopped.
3.3.3 Four Way Valve Operation Compensation
Outline
At the beginning of operation as the four way valve is switched, the pressure difference to
activate the four way valve is acquired when the output frequency is higher than a certain fixed
frequency, for a certain fixed time.
Detail
Starting Conditions
1. When the compressor starts and the four way valve switches from OFF to ON
2. When the four way valve switches from ON to OFF during operation
3. When the compressor starts after resetting
4. When the compressor starts after the fault of four way valve switching
The lower limit of frequency keeps A Hz for B seconds with any conditions 1 through 4 above.
A (Hz)
B (seconds)
39
ON condition
Discharge pipe temperature < B°C
OFF condition
Discharge pipe temperature > C°C
Radiation fin temperature ≥ 90°C
ON condition
Discharge pipe temperature < D°C
OFF condition
Discharge pipe temperature > E°C
Radiation fin temperature ≥ 90°C
A (°C)
B (°C)
–2.5
0
20/25/35 class
Cooling
Heating
68
45
C (°C)
D (°C)
2
10
50 class
Cooling
Heating
66
48
70
SiBE041401E
E (°C)
12
Function and Control