RX15/18/24FVJU
4.7
Removal of the Electronic Expansion Valve
Procedure
Step
Remove the
electronic
1
expansion valve
coil.
Remove the sheets of
2
putty.
Before working,
make sure that the
refrigerant is empty
in the circuit.
Heat up the two brazed
3
parts of the
electronic
expansion valve
and
disconnect.
Be sure to apply
nitrogen
replacement when
heating up the
brazed part.
276
Warning
Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Procedure
SiUS04-702
Points
Caution
Be careful about the
electronic expansion valve,
pipes and so on, which were
heated up by a gas brazing
machine, so as not to get
burnt your hands.
Warning
Ventilate when refrigerant
leaks during the work.
(If refrigerant contacts fire, it
will cause to arise toxic gas.)
Removal Procedure