ALPHABETIC REFERENCE
ID___Off_Prio_3
ID___Man_load_she
d
ID___On_Prio_3
ID___On_Prio_2
ID___On_Prio_1
ID___Rotating_P1
ID___Rotating_P2
ID___Rotating_P3
Counter_Zi
74-5577–33 (US)
EN2B-0184 GE51 R0518 (Europe)
VD
Input/
Input:
Output
0:
There is no load to switch off in priority group 3
1:
There is at least one load to switch off in priority group 3
Output:
0:
Reset of the loads-available-to-turn-off detection for the
priority group 3
VD
Output
0:
Signal to initiate an alarm and inform about the necessity
of manual load shedding
1:
Signal is not active
(Set Active State of this point to 1)
VD
Input/
Input:
Output
0:
There is no load to switch on in priority group 3
1:
There is at least one load to switch on in priority group 3
Output:
0:
Reset of the loads-available-to-turn-on detection for the
priority group 3
Input:
VD
Input/
Output
0:
There is no load to switch on in priority group 2
1:
There is at least one load to switch on in priority group 2
Output:
0:
Reset of the loads-available-to-turn-on detection for the
priority group 2
VD
Input/
Input:
Output
0:
There is no load to switch on in priority group 1
1:
There is at least one load to switch on in priority group 1
Output:
0:
Reset of the loads-available-to-turn-on detection for the
priority group 1
VD
Output
0:
Load switching is sequential in priority group 1
1:
Load switching is rotational in priority group 1
VD
Output
0:
Load switching is sequential in priority group 2
1:
Load switching is rotational in priority group 2
VD
Output
0:
Load switching is sequential in priority group 3
1:
Load switching is rotational in priority group 3
PI
Input
Connection to reset the Totalizer Input to avoid overflow when its
value becomes too large (see Totalizer Input Reset in the General
Functions section)
NOTE: You must assign the STARTUP user address to the user address for the
CARE STARTUP point.
Type abbreviations:
DI: Digital input
VA: Virtual (pseudo) analog
VD: Virtual (pseudo) digital
PI: Physical input
94